Advanced Programming
38
06
1
2
3
4
5
Residential Dial
- This communication format works as fol-
lows:
If an event occurs that is programmed to communicate, the
panel will seize the line and dial the appropriate telephone
number(s).
Once the dialing is complete, the panel will proceed to emit
the ID tone (1300 Hz for 500 ms every 2 sec).
The panel then waits for a handshake (any DTMF digit except
digits 3,6 and 9) from any phone. It will wait for this hand-
shake for the duration of “
Post Dial Wait for Handshake
”
(
section [161]
).
Once the panel receives the handshake, it will emit an alarm
tone over the phone line (1300Hz/1500Hz for a time of
500ms on / 500ms off).
This alarm tone will be emitted for 20 seconds.
If multiple alarms occur, only one call will be made to each
phone number that the panel is programmed to dial.
☞
The DTMF Digits 3, 6, and 9 are not valid handshakes!
07
10 bps, 1400 Hz Handshake
08
10 bps, 2300 Hz Handshake
[360] Communicator Format Options
1
Default
04
I___I___I
1st Telephone No.
2
Default
04
I___I___I
2nd Telephone No.
☞
1600Hz Handshake for bps formats may be selected in
sec-
tion [702] option. 4
.
☞
The 3rd Telephone No. follows the format of the 1st Tele-
phone No.
[361- 368] Communicator Call Directions
All reporting codes belong to one of the five reporting groups
indicated below. The control panel can call two different
phone numbers for each
Call Direction Group ([361] -
[368]
). These sections specify which number will be called for
a specific event. The third telephone number can only be
used as a backup or alternate for the first telephone number
[361] System Alarms and Restorals
1
ON
1st Telephone No.
✓
OFF 1st Telephone No. Disabled
2
ON
2nd Telephone No.
OFF 2nd Telephone No. Disabled
✓
3-8
Future Use
[363] System Tampers and Restorals
1
ON
1st Telephone No.
✓
OFF 1st Telephone No. Disabled
2
ON
2nd Telephone No.
OFF 2nd Telephone No. Disabled
✓
3-8
Future Use
[365] System Openings and Closings
1
ON
1st Telephone No.
✓
OFF 1st Telephone No. Disabled
2
ON
2nd Telephone No.
OFF 2nd Telephone No. Disabled
✓
3-8
Future Use
[367] System Maintenance Alarms and Restorals
1
ON
1st Telephone No.
✓
OFF 1st Telephone No. Disabled
2
ON
2nd Telephone No.
OFF 2nd Telephone No. Disabled
✓
3-8
Future Use
[368] System Test Transmissions
1
ON
1st Telephone No.
✓
OFF 1st Telephone No. Disabled
2
ON
2nd Telephone No.
OFF 2nd Telephone No. Disabled
✓
3-8
Future Use
[370] Communication Variables
[1] Swinger Shutdowns (Alarms & Restorals)
This value defines the number of attempts (alarm and restoral pairs)
per zone that the communicator will make before it shuts down for
that zone (“swinger shutdown”). Program a 3 digit number from
000 to 014. When programmed as 000, the communicator will not
be shut down and all alarms will be transmitted.
☞
The event buffer can also follow swinger shutdown if
enabled. See section [013]
Default
003
I___I___I___I
000-014 transmissions
[2] Swinger Shutdowns (Tampers & Restorals)
This value defines the number of times the same system tamper type
event will occur before stopping transmissions.000= disabled
Default
003
I___I___I___I
000-014 transmissions,
[3] Swinger Shutdowns (Maintenance & Restorals)
This value defines the number of times the same system mainte-
nance (Trouble) type event will occur before stopping transmissions.
☞
Fire Troubles will follow the Maintenance Swinger
Shutdown. Swinger shutdown is enabled on zone
types
[01]-[06]
and
[25]
by default.
Default
003
I___I___I___I
000-014 transmissions