Figure 3: 3G4010CF Module Wiring Diagram - Standalone Configuration
These inputs are typically used to
interface with fire alarm panels that do
not have a dialer interface and use the
fire alarm, fire supervisory or fire
trouble output relay contacts to send
the events to the communicator.
3G4010CF
Connect relay contacts to a zone
input on the alarm control panel
for 3G4010CF troubles supervision
(24 h type zone)
NOTE:
If the control panel PGM output connected to the 3G4010CF input latches (remains closed) after an alarm has
occurred, the 3G4010CF input will remain active. The latched PGM output must be reset or future alarms will not be reported
via the zone input of the 3G4010CF and additional alarms may be triggered when the 3G4010CF is locally or remotely restar-
ted. Please contact panel vendor for details on how to reset the control panel PGM.
Figure 4: Power Supply Wiring Diagram
PS4085
+12V COM ACT LBT TEST
+BAT
AC IN
TEST - CHARGER TROUBLE OUTPUT 50mA, 12V Max.
LBT - LOW BATTERY OUTPUT 50mA, 12V Max.
ACT - AC FAILURE OUTPUT 50mA,12V Max.
Primary
120VAC
60Hz, 0.3A
TRANSFORMER
ATC Frost Model FTC3716
SPECIAL APPLICATION OUTPUT
RATING
: 11.5V
DC
- 12.6V
DC
,
700mA max. Use for DSC,
Model 3G4010CF
WARNING!
HIGH VOLTAGE. DISCONNECT AC
POWER & TELEPHONE LINES
PRIOR TO SERVICING
These outputs shall be connected to zone inputs of an alarm control panel in order to provide the required trouble supervision
(visual and audible indication required at the control panel). The outputs are active low (switched to ground) and can be con-
nected to a control panel directly or by using a listed supervision relay (suggested model: DSC, RM-2 or RM1C).
19