background image

l

Remote Diagnostics

l

Panel Format Detection

l

SMS Command and Control

l

Phone number call direction

l

Easy enrollment with C24 Communications via VRU, web or mobile interface

NOTE:

The 3G4010CF is designed to work with the Contact ID communication format as described in SIA DC- 05 Standard or

the SIA communication format as described in SIA DC-03 Standard. Before completing the field installation of the alarm mon-
itoring system, please ensure communication with the supervising station is successful by sending several events and con-
firming that they have been received.

Technical Specifications

Ratings

Power Supply Ratings

Input Voltage:

120V/60Hz/0.3A

Standby Voltage:

12V/7AH

Standby Time:

24h (NSC) plus 5 minutes alarm

Low Battery Trouble
Indication Threshold:

11.5VDC

Battery Deep Discharge
Protection (cut-off):

9.5VDC

Battery Type:

sealed, rechargeable type, rated 12V/7Ah

(for 24hr standby time)

Battery charging voltage:

13.75Vdc

Battery charge current:

700mA (maximum)

NOTE: Battery must be replaced every 3-5 years.
Operating frequency - 2G
(GSM/GPRS/EDGE):

850/1900MHz

Operating frequency - 3G
(UMTS/HSPA):

850/1900MHz

Antenna gain:

2.0dBi

Environmental
Specifications

Operating temperature:

0°C-49°C (32°F-120°F)

Humidity:

93%RH Maximum (non-condensing)

Mechanical Specifications

Enclosure Type

metal, red, hardwired transformer and high voltage connection box included

Enclosure Dimensions:

290mm x 254mm x 75mm (11.5" x 10" x 3")

Weight:

5.8Kg (12.8 lbs) (including standby battery)

Simulated Telco Loop specifications (TIP/RING)

On-Hook Voltage:

12Vdc

Off-Hook Voltage
(Maximum):

22Vdc

Loop Current :

25mA

Loop Resistance :

600 Ohms

Standard Battery Capacity

The calculation for battery capacity is based on 200mA standby current for 24 hours plus a five minute alarm at 400mA or
600mA (if the 4 PGM outputs are also activated)
The requirements are as follows:
200mA x 24h = 4800mAh capacity for standby
400mA x 5/60h= 33.33mAh capacity for alarm condition
Total = 4833.33 mAh needed for 24h and five minutes alarm transmission. The supplied battery is 7Ah.

4

Summary of Contents for 3G4010CF

Page 1: ...ercial RF Communicator 3G HSPA Network Signaling Devices INSTALLATION MANUAL V4 0 Warning This manual contains informationon limitations regarding product use andfunction and inform ationonthelimitati...

Page 2: ...Principles 10 Simulated Landline Mode 10 Panel Transmission Monitoring PTM 10 Cellular Communications Sequence 11 Inputs 11 Outputs 11 Activating the Outputs 11 Reporting Codes 12 Swinger Shutdown 12...

Page 3: ...uper vision window for reporting single technology communicator trouble shall be set to five minutes However the product can be installed in accordance with the requirements ofNFPA72 2013 edition whic...

Page 4: ...ng voltage 13 75Vdc Battery charge current 700mA maximum NOTE Battery mustbe replaced every 3 5 years Operating frequency 2G GSM GPRS EDGE 850 1900MHz Operating frequency 3G UMTS HSPA 850 1900MHz Ante...

Page 5: ...3G Antenna 2 Metal Casing 3 Antenna Mounting Hardware 4 Antenna Connector 5 Anchor Screw Holes 3mm 6 SIM Card Holder 7 3G HSPA Radio Module 8 Status LEDs See page 1 Part 9 PC Link Connector 10 Tamper...

Page 6: ...eatsent The 3G4010CF is designed to work with the ContactID com munication formatas described in SIADC 05 Standard or the 300 baud SIA communication formatas described in SIA DC 03 standard Every 24 h...

Page 7: ...ll move to Step 3 and scan for carriers with sufficientsignal strength and attach to the carrier Ifthe 3G4010CF is connected to a carrier with sufficientsignal strength min imum ofbottom signal streng...

Page 8: ...reen Top Yellow Green Bottom ON ON ON FLASHING and turn on solid when itreceives a communication back from the central station Red Blue Yellow Green Top Yellow Green Bottom ON ON ON ON Ifat leastone o...

Page 9: ...iate an AC trouble by flashing the RED status LED 9 times and will delay the AC loss eventtransmission by one hour LBT Battery Trouble This open collector outputactivates when a Battery Trouble condit...

Page 10: ...ndline has been restored the 3G4010CF switches the connected device back to the landline OR l Ifthe landline is still down the 3G4010CF continues the simulation until the landline is restored The 3G40...

Page 11: ...ContactID or SIA formatwith Inputs 1 4 reporting as 991 to 994 respectively Defaultsettings are INPUT 1 AC LOSS INPUT 3 FIRE ALARM INPUT 2 FIRE SUPERVISORY INPUT 4 SYSTEM TROUBLE Inputs can be config...

Page 12: ...oes notsupportremote programming local hardware defaultrequired Upon activation through Con nect24 the productwill operate as described in this manual Swinger Shutdown To prevent runaway signals to th...

Page 13: ...on offtogether indicates the radio is notready This LED sequence will display until the low battery voltage is restored and the radio is enabled again SMS Command and Control NOTE For UL ULC installa...

Page 14: ...uage Command Label shallnot be case sensitive English Disarm French Desarmement Spanish Desarmado l Activate PGM Language Command Label shallnot be case sensitive English Activate French Activation Sp...

Page 15: ...gnal Strength 14 l Unitcan be installed in the currentmounting location Top LED FLASHING with bottom LED ON Excellent Signal Strength 11 13 l Unitcan be installed in the currentmounting location Botto...

Page 16: ...e antenna cable is plugged securely into the radio connector l Ifthe SIM is active connecta battery to the unitand testvarious locations for good excellentsignal strength l Connectan antenna extension...

Page 17: ...connector Gently turn the screwdriver away to pop outthe connector from the modem l To install the antenna firmly push the connector into the modem until it snaps into place Enrolling a 3G4010CF l Th...

Page 18: ...0CF with PC5700 Interface Use No 26 AWG wires for the connection to PSTN Phone line connection is required only for back up configurations In stand alone applications no other communication technology...

Page 19: ...gered when the 3G4010CF is locally or remotely restar ted Please contactpanel vendor for details on how to resetthe control panel PGM Figure 4 Power Supply Wiring Diagram PS4085 12V COM ACT LBT TEST B...

Page 20: ...6 19 Z4 Z3 Z2 COM 20 Z1 AUX PGM 3 PGM 1 PGM 4 COM 3G4010CF PGM 3 DC IN DSC Supervision Relay See Note Power Supply Provides power to the 3G4010CF Module NOTES 1 Program the zone pointas Supervisory ty...

Page 21: ...nycopiesof the SOFTWARE PRODUCT are owned by DSC or its suppliers You may not copythe printed materialsaccompanying the SOFTWAREPRODUCT Alltitle and intellectualpropertyrightsin and to the contentwhic...

Page 22: ...ission public service commission orcorporation commission for information Alarm dialling equipment must be able to seize the telephone line and place a call in an emergency situation Itmustbe able to...

Page 23: ...acilitiesorservices down time pur chaser stime the claimsof third parties including customers and injury to prop erty The laws of some jurisdictions limit or do not allow the disclaimer of consequenti...

Page 24: ...o willaggressively enforce its intellectualproperty rightsto the fullestextent ofthe law including pursuitofcriminal prosecution wherever necessary All trademarksnotowned byTyco are the propertyofthei...

Reviews: