29
F_14
: Stopping method range:
= 000: Controlled deceleration stop
= 001: free run to stop
F_15
: DC braking time / free run start range:
= 00.0~25.5 sec.
F_16
: DC braking starting frequency
= 1~10 Hz
F_17
: DC braking level
= 0~20%
If F_14 = 0
When the inverter receives the stop command, it decelerate to the pre-set frequency setup by F_16
after this the output voltage level that is set in the F_17; will determine the amount of DC voltage that’s
injected into the motor. The time duration to perform this stopping function is setup in F_15.
If F_14 = 1
The inverter stops output immediately after receiving the stop command. The motor will enter into a free
running state until it comes to a complete stop.
DC injection braking is disabled when F_14=1.
F_15 becomes free-run start delay to provide
sufficient time for the mechanical brake to stop
motor rotation before restarting the motor.
Frd
Note: Display shows
Frd
during free run start delay time.