1BHF " t %3*45&&. 7BQPSMPHJD *OTUBMMBUJPO BOE 0QFSBUJPO .BOVBM
Appendix
A p p e n d i x :
G T S m o d e l - s p e c i f i c
d e f a u l t s e t u p v a l u e s
Table A-4-1:
GTS model-specific default setup values
GTS
model
Water
type
EOS
drain
enabled?
Drain valve
type*
Water usage before auto drain/flush
Drain
duration
Flush
duration
Skim
duration
EOS
drain
duration
Water usage
before service
Tube dispersion systems
Area-type dispersion systems
lbs
kg
lbs
kg
Minutes
Minutes
Seconds
Minutes
lbs
kg
GTS-100
Potable
:FT
Electric motorized
25,000
11,300
25,000
11,300
40
1
25
75
75,000
34,000
Softened
:FT
Electric motorized
75,000
34,000
25,000
11,300
40
1
25
75
75,000
34,000
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
150,000
68,000
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
30
150,000
68,000
GTS-200
Potable
:FT
Electric motorized
25,000
11,300
25,000
11,300
40
1
25
75
150,000
68,000
Softened
:FT
Electric motorized
150,000
68,000
25,000
11,300
40
1
25
75
150,000
68,000
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
300,000
136,100
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
30
300,000
136,100
GTS-300
Potable
:FT
Electric motorized
30,000
13,600
30,000
13,600
45
1
30
90
225,000
102,000
Softened
:FT
Electric motorized
225,000
102,000
30,000
13,600
45
1
30
90
225,000
102,000
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
450,000
204,100
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
35
450,000
204,100
GTS-400
Potable
:FT
Electric motorized
30,000
13,600
30,000
13,600
45
1
30
90
300,000
136,100
Softened
:FT
Electric motorized
300,000
136,100
30,000
13,600
45
1
30
90
300,000
136,100
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
600,000
272,200
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
35
600,000
272,200
GTS-500
Potable
:FT
Electric motorized
45,000
20,400
45,000
20,400
65
2
45
130
375,000
170,100
Softened
:FT
Electric motorized
375,000
170,100
45,000
20,400
65
2
45
130
375,000
170,100
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
750,000
340,200
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
50
750,000
340,200
GTS-600
Potable
:FT
Electric motorized
45,000
20,400
45,000
20,400
65
2
45
130
450,000
204,100
Softened
:FT
Electric motorized
450,000
204,100
45,000
20,400
65
2
45
130
450,000
204,100
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
900,000
408,200
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
50
900,000
408,200
GTS-700
Potable
:FT
Electric motorized
50,000
22,700
50,000
22,700
80
2
55
160
525,000
238,100
Softened
:FT
Electric motorized
525,000
238,100
50,000
22,700
80
2
55
160
525,000
238,100
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1,050,000
476,300
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
60
1,050,000
476,300
GTS-800
Potable
:FT
Electric motorized
50,000
22,700
50,000
22,700
80
2
55
160
600,000
272,200
Softened
:FT
Electric motorized
600,000
272,200
50,000
22,700
80
2
55
160
600,000
272,200
DI/RO
No
Ball
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1,200,000
544,300
:FT
Electric damper
N/A
N/A
N/A
N/A
N/A
N/A
N/A
60
1,200,000
544,300
Notes:
* GTS units in an outdoor enclosure always have an electric damper drain valve. All GTS drain valves are normally closed except for GTS units in an outdoor enclosure, which have normally open drain valves.
EOS = End-of-season