Installation
4. Connect to the humidifier.
a. Using a computer connected to the Vapor-logic4 board,
open a Web browser such as Mozilla® Firefox® or Internet
Explorer®.
b. Find the browser address bar (see Figure 21-1), delete
all existing text in the browser address bar, type the
Vapor-logic4 default IP address into the browser’s address
bar:
192.168.1.195
and press Enter.
Connecting Web interface directly to a computer on a network
CAUTION!
Before you connect a Vapor-logic4 device to a network,
please contact your IT department. Given that the Vapor-logic4
controller ships with a static IP address, it is important to ensure
that there is not another device with that same IP address already
on the network. Working with your IT department before network
connection will help ensure the integrity of the network and the
devices on that network.
If your network uses DHCP (Dynamic Host Configuration
Protocol), use the keypad/display to navigate to:
Setup/Communications/Network IP Address. Enable DHCP and
restart the Vapor-logic4 board.
CAUTION!
When DHCP is enabled, the server can dynamically
change the IP address of Vapor-logic4, making existing bookmarks
unusable. The most current IP address can always be found by
using the keypad/display to navigate to:
Set-Up/Communications/Network IP Address.
Important:
DHCP cannot be enabled from the Web interface; it
must be enabled using the keypad/display.
Other communication connections
For BACnet or LonTalk installation instructions, see Page 64.
For multiple-tank installation instructions, see Page 70.
F i e l d w i r i n g :
C o m m u n i c a t i o n c o n n e c t i o n s
Enter the IP address in your browser’s address bar
Figure 21-1:
Entering the IP address