RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Piping:
INSTALLATION
Supply water piping may be of any code-approved material (copper, steel, or
plastic). The fill valve connection size is a 3/4" pipe thread (DN20) fitting. In
cases where water hammer may be a possibility, consider installing a shock
arrestor. Water pressure must be between 25 psi and 80 psi (175 kPa and
550 kPa).
Important:
Install unions in the water supply and drain lines as shown in
Figure 19-1 to allow tank removal.
Supply water piping
CAUTION
Excessive supply water pressure
Supply water pressure greater than 80
psi (550 kPa) can cause the humidifier
to overflow.
Unions by installer
1" NPT or BSP (DN25)
tank drain, skimmer
and p-trap piping,
Rated for 212 °F (100
°C), if piping runs over
10' (3m) increase size
to 1¼" (DN32) after
p-trap
1" (25.4 mm) air gap
Spill funnel. Plumb
to floor drain
Open floor drain
OM-8109
Supply water
Steam hose (maximum run 10' [3 m]).
May also use tubing.
Water supply line:
• 3/4" NPT or BSP (DN20)
connection size
• 25 to 80 psi (175 to
550 kPa) required water
pressure.
Water shock arrester recommended,
by Installer
Inline strainer
FIGURE 22-1: RTS HUMIDIFIER FLOOR STAND PIPING OVERVIEW FOR -3 AND -4 UNITS