RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
Overview
The best way to determine how often your humidifier needs maintenance is to
remove the heater plate and inspect it for mineral deposits after three months of
operation. Hours of operation and duty cycle will determine your maintenance
schedule, as will water quality.
WATER QUALITY AND MAINTENANCE
Maintenance requirements vary with water quality, because tap and softened
water carry a variety of minerals and other materials in a mix that varies from
location to location. Very hard (high mineral content) water requires more
frequent cleaning and drain/flush cycles than water with low mineral content.
RO water and softened water significantly reduce mineral accumulation inside
the humidifier.
Note: Solids, like silica, are not removed in the softening process.
MAINTENANCE
WARNING
Electric shock hazard
Contact with energized circuits can cause severe personal injury or death as a result
of electric shock. To prevent shock, disconnect electrical power before performing
service or maintenance procedures on an part of the humidification system.
When performing maintenance on the humidifier:
• Always switch the Vapor-logic display control mode to Standby.
• Place all power disconnects in OFF position and lock in OFF position.
• Close the field-installed manual supply water shut-off valve.
WARNING
Thermal cut-out component is critical to
the safety of this equipment: use only
DriSteem replacement part.