RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
• Clean heating elements.
• Install the probe and probe plug assembly. Verify ground wire is
solidly connected to tank.
• Replace probe assembly gasket.
• Replace heater plate/tank gasket.
• Re-install the heater plate cover on the tank.
• Provide 60 lb-in torque for heater plate nuts during reinstallation
• Reconnect the heater electrical plug.
• Verify electrical connections:
• Verify that all DIN rail-mounted components are securely fastened to
DIN rail.
• Verify that all power terminal screws and lugs are tight from power
block to heaters.
• Verify that all plugs under the humidifier cover are completely
plugged in.
• Turn on the water supply.
• Turn on the electrical power.
3. Off-season maintenance
• Perform complete inspection and cleaning of the following:
• Heaters
• Probe rods
• Skimmer port and water seal
• Humidifier tank
• After cleaning, the humidifier should remain empty until humidification is
required.
Humidifier De-scaling Solution
Scale buildup on humidifier heaters acts as
an insulator, reducing humidifier performance
while increasing energy costs. To keep
humidifiers operating as efficiently as possible,
remove scale with DriSteem's Humidifier De-
scaling Solution, available for purchase from
your DriSteem representative.
The De-scaling Solution cleans without risk
of corroding humidifier tanks or welds. The
De-scaling Solution also cleans surfaces
unreachable by hand scraping.
DriSteem's Humidifier De-scaling Solution is the
only approved cleaner/de-scaler for use with
DriSteem humidifiers. Use of other cleaners/de-
scalers may void your DriSteem warranty.
Inspection and maintenance
MAINTENANCE