RTS HUMIDIFIER RX SERIES INSTALLATION, OPERATION, AND MAINTENANCE MANUAL
SPECIFICATIONS
Table 6-1:
RTS humidifier capacities, electrical specifications (Europe)
RTS model
230V Single Phase
400V Three Phase
Maximum Steam
Power
Total
Maximum
Current
Draw
Heater
Configuration*
Maximum Steam Capacity
Power
Total
Maxi-
mum
Current
Draw
Heater
Configuration
lbs/hr
kg/hr
kW
amps
lbs/hr
kg/hr
kW
amps
RX-6-1
5.5
2.5
2
8
1-003
—
—
—
—
—
RX-12-1
11
5.0
4
16
1-009
12
5.4
4
8.70
2-005
RX-18-1
16.5
7.5
6
24
1-016
18
8.2
6
8.70
3-005
RX-24-1
22
10.0
8
31.9
2-009
24
10.9
8
13.00
2-005, 1-011
RX-30-1
27.6
12.5
10
39.9
1-009, 1-016
30
13.6
10
17.30
1-005, 2-011
RX-36-1
33.1
15.0
12
47.92
2-016
36
16.3
12
17.30
3-011
RX-42-1
—
—
—
—
—
42
19.0
14
21.70
2-011, 1-019
RX-48-1
—
—
—
—
—
48
21.8
16
26.00
1-011, 2-019
RX-63-1
—
—
—
—
—
63
28.6
21
32.5
2-019, 1-025
RX-75-1
—
—
—
—
—
75
34.0
25
39
3-025
RX-30-2
—
—
—
—
—
—
—
—
—
—
RX-36-2
—
—
—
—
—
—
—
—
—
—
RX-48-2
44.1
20.0
16
63.9
4-009
—
—
—
—
—
RX-63-2
66.1
30.0
21
95.8
4-016
—
—
—
—
—
RX-75-2
—
—
—
—
—
—
—
—
—
—
RX-90-2
—
—
—
—
—
90
40.8
30
52
2-011, 4-019
RX-102-2
—
—
—
—
—
102
46.3
34
52
6-019
RX-126-2
—
—
—
—
—
126
57.1
42
65
4-019, 2-025
RX-144-2
—
—
—
—
—
144
65.3
48
77.9
2-019, 4-025
RX-162-2
—
—
—
—
—
162
73.5
54
77.9
6-025
• All RTS humidifier models operate at 50/60 Hz.
• For wire sizing, the highest leg draw is shown due to current imbalance.
• *600931 are the first digits of the heater part number.
• Maximum amps is determined based on the heaters used by each model. Some voltage/kW combinations show higher amperage values than
what the unit capacity will allow.
Models, capacities, and electrical specifications (Europe)