Operational Characteristics
14
Manual Zero Calibration of the Output Signal.
Deactivate alarm activation of the central device.
1
Expose the gas transmitter to nitrogen, synthetic air, and/or fresh air via calibra-
tion adapter and wait until measurement value stabilises.
2
Place the magnetic pin onto the transmitter surface area marked by the "
"
icon and hold it there (within the black frame) for at least five seconds. After five
seconds, the output signal of the gas transmitter switches to the display of the
span gas signal (3 mA) for as long as the magnetic pin is held against it. At the
same time, a zerosetting of the optical measuring unit is carried out automatical-
ly.
3
Remove the magnetic pin. The output signal of the gas transmitter moves back
to the previously displayed value. The device is now set to zero point calibration
routine. Within this routine, the output signal will decrease resp. increase, depen-
ding on whether the magnetic pin is placed on one of the areas marked with eit-
her the "
" or the "
" icon.
4
Adjust the zero point signal by placing the magnetic pin on one of the areas mar-
ked with either the "
" or the "
" icon.
5
Remove the magnetic pin. The device terminates the zero point calibration rou-
tine after 30 seconds without further settings being carried out. As confirmation
of the successful calibration, the output signal changes back to the span gas si-
gnal (3 mA). This signal is indicated for the same period of time as when starting
the zerosetting calibration routine.
6
Terminate exposure to gas.
Reactivate alarm activation of the central device.
NOTICE
The calibration is automatically terminated and new calibration parameters are not saved if the gas concentration measured
by the gas transmitter changes during the calibration procedure (e.g. because the calibration gas cylinder fell empty during
the calibration procedure). In this case, the gas transmitter returns to normal operation without displaying the span gas signal
as confirmation.
0
S
00823812_01.eps
0
0
S
0
S
00923974_02_en.eps
S
0
0
time
display
–6.25 %LEL
(3 mA)
0
I
(1)
I (2) I
(3)
I
(4)
I (5)
I (6)
Summary of Contents for PIR 3000
Page 1: ...Dräger PIR 3000 en Infrared Gas Transmitter Instructions for Use 00123812_02 eps 0 S ...
Page 25: ...25 Technical Data Dimensions 01123812_01_en eps 0 S aprox 170 mm ø 37 mm M25 x 1 5 or 3 4 NPT ...
Page 28: ...ATEX Approval 28 ATEX Approval ...
Page 29: ...29 ATEX Approval ...
Page 30: ...ATEX Approval 30 ...
Page 31: ...31 ATEX Approval ...
Page 32: ...ATEX Approval 32 ...
Page 33: ...33 ATEX Approval ...
Page 34: ...ATEX Approval 34 ...
Page 35: ...35 ATEX Approval ...
Page 36: ...ATEX Approval 36 ...
Page 37: ...37 ATEX Approval ...
Page 38: ...ATEX Approval 38 ...
Page 39: ...39 ATEX Approval ...
Page 40: ...ATEX Approval 40 ...
Page 41: ...41 ATEX Approval ...
Page 42: ...ATEX Approval 42 ...
Page 43: ...43 ATEX Approval ...
Page 44: ...ATEX Approval 44 ...
Page 45: ...45 ATEX Approval ...
Page 46: ...ATEX Approval 46 ...
Page 47: ...47 ATEX Approval ...
Page 48: ...IECEx Approval 48 IECEx Approval ...
Page 49: ...49 IECEx Approval ...
Page 50: ...IECEx Approval 50 ...
Page 51: ...51 IECEx Approval ...
Page 52: ...IECEx Approval 52 ...
Page 53: ...53 IECEx Approval ...
Page 54: ...UL Approval 54 UL Approval ...
Page 55: ...55 UL Approval ...
Page 56: ...UL Approval 56 ...
Page 57: ...57 CSA Approval CSA Approval ...
Page 58: ...CSA Approval 58 ...
Page 59: ...59 CSA Approval ...
Page 60: ...Declaration of Conformity 60 Declaration of Conformity ...
Page 61: ......
Page 62: ......
Page 63: ......