11
Operational Characteristics
Operational Characteristics
The gas transmitter generates an output signal which is proportional to the
measured gas concentration. The factor of proportionality between displayed value
and the measured gas concentration is determined by the span calibration of the
gas transmitter (see "Manual Span Calibration of the Output Signal." on page 15).
The gas transmitter regularly runs self tests for numerous internal functions. As
soon as a divergence from normal operation is detected, the device will issue a
fault message.
Output Signals of the Device:
Calibration
A functional check and - if necessary - a calibration must be carried out regularly for
gas warning systems (see page 20, Maintenance).
Zero gas and test gas are to be applied for functional check and calibration of the
infrared gas transmitter Dräger PIR 3000. To this end, the gas is applied either with
— the calibration adapter in connection with the splash guard (see page 5, part of
the scope of delivery) or
— the gas exposure / process adapter (see page 6 and order list) or
— the dirt deflector in connection with the splash guard (see order list).
The required gas flow rate for functional check and calibration is as follows:
— 0.5 to 1 L/min. for the calibration adapter with splash guard and the dirt deflector
with splash guard in closed rooms at wind speeds up to 5 m/s (3 Beaufort),
— 1 to 2 L/min. for the calibration adapter with splash guard and the dirt deflector
with splash guard at wind speeds up to 27 m/s (10 Beaufort),
— 0.5 to 3 L/min. for the gas exposure / process adapter.
Display of
Output Signal
zero point
4 mA
full scale deflection
20 mA
under-range
3.8 mA to 4 mA
over-range
20.0 mA to 20.5 mA
span gas signal to indicate begin and
successful termination of gas transmitter
calibration via magnetic pin
3 mA
Fault and inlet signal (during self check
and running-in period)
1 mA
Warning (while increasing the Drift of the
zero point into the negative range)
2 mA
Summary of Contents for PIR 3000
Page 1: ...Dräger PIR 3000 en Infrared Gas Transmitter Instructions for Use 00123812_02 eps 0 S ...
Page 25: ...25 Technical Data Dimensions 01123812_01_en eps 0 S aprox 170 mm ø 37 mm M25 x 1 5 or 3 4 NPT ...
Page 28: ...ATEX Approval 28 ATEX Approval ...
Page 29: ...29 ATEX Approval ...
Page 30: ...ATEX Approval 30 ...
Page 31: ...31 ATEX Approval ...
Page 32: ...ATEX Approval 32 ...
Page 33: ...33 ATEX Approval ...
Page 34: ...ATEX Approval 34 ...
Page 35: ...35 ATEX Approval ...
Page 36: ...ATEX Approval 36 ...
Page 37: ...37 ATEX Approval ...
Page 38: ...ATEX Approval 38 ...
Page 39: ...39 ATEX Approval ...
Page 40: ...ATEX Approval 40 ...
Page 41: ...41 ATEX Approval ...
Page 42: ...ATEX Approval 42 ...
Page 43: ...43 ATEX Approval ...
Page 44: ...ATEX Approval 44 ...
Page 45: ...45 ATEX Approval ...
Page 46: ...ATEX Approval 46 ...
Page 47: ...47 ATEX Approval ...
Page 48: ...IECEx Approval 48 IECEx Approval ...
Page 49: ...49 IECEx Approval ...
Page 50: ...IECEx Approval 50 ...
Page 51: ...51 IECEx Approval ...
Page 52: ...IECEx Approval 52 ...
Page 53: ...53 IECEx Approval ...
Page 54: ...UL Approval 54 UL Approval ...
Page 55: ...55 UL Approval ...
Page 56: ...UL Approval 56 ...
Page 57: ...57 CSA Approval CSA Approval ...
Page 58: ...CSA Approval 58 ...
Page 59: ...59 CSA Approval ...
Page 60: ...Declaration of Conformity 60 Declaration of Conformity ...
Page 61: ......
Page 62: ......
Page 63: ......