SECONDARY DOCKING PORT • SOFTWARE DETAILS
Modem Unit String
Number of Rings enter the number of
rings that the KDA should wait before
answering an incoming call.
Callout Delay
Sets the minimum time that the KDA will
wait after a previous dialout attempt to
either call in a new alarm or call an alter-
nate number if a previous alarm was not
acknowledged.
Baud
Select from
OFF
,
1200
,
2400
or
9600
,
normally set to 1200.
Status Report Interval
The time period between periodic alarm
status reports dialed from the KDA to
T/Mon. A value of 0 for both hours and
minutes disables periodic status report-
ing.
Dialout Alarm Reporting
Determines when the KDA will use the
dialup link to report alarms (as opposed
to normal reporting via fixed connection
on the primary port). This entry works in
conjunction with an entry on the Alarms
definition page for each individual alarm:
• When
NORMAL
, calls whenever a
DIALALARM
occurs, as specified on
the Alarms page.
• When
BACKUP
, calls only when the
primary port has failed, may be
enabled-or disabled for individual
alarms on the
Alarms
page.
D-SW-709
UM00C.08103
October 22, 2001
www.dpstele.com
Summary of Contents for KDA 864
Page 4: ...SOFTWARE DETAILS D SW 709 UM00C 08103 October 22 2001 www dpstele com Software Details ...
Page 29: ...NOTES 1 26 D SW 709 UM00C 08103 October 22 2001 www dpstele com ...
Page 30: ...TROUBLESHOOTING 2 1 Troubleshooting D SW 709 UM00C 08103 October 22 2001 www dpstele com ...
Page 34: ...3 1 EXPANSION CARDS Expansion Cards D SW 709 UM00C 08103 October 22 2001 www dpstele com ...
Page 43: ...APPENDIX Appendix 4 1 D SW 709 UM00C 08103 October 22 2001 www dpstele com ...