![DPS Telecom D-PK-NG216 User Manual Download Page 23](http://html1.mh-extra.com/html/dps-telecom/d-pk-ng216/d-pk-ng216_user-manual_2525724023.webp)
19
Note:
Each jumper inserts a 250-ohm shunt resistor across the input. This must be taken into
account when defining the analog input reference scale.
+
Current
Voltage
+
Jumper installed for current
Jumper removed for voltag e
Unjumpered/Open Position:
Voltage Operation (default)
Jumpered/Closed Position:
Current Operation
4 to 20 mA
Current Source
Transducer
Voltage Source
Transducer
Analog
Channel
Input
-
-
Analog
Channel
Input
250 Ohm
Shunt
Jumper
Analog
J20
ANA 1
J21
ANA 2
J22
ANA 3
J23
ANA 4
Jumper settings for analog alarms inputs.
5. Slide the top cover of the case back into position and replace the screws.
6. Reconnect and power up the NetGuardian.
5.8.2
Analog Step Sizes
Analog Step Sizes
Input Voltage Range
Resolution (Step
Size)
Accuracy
0-5 V
.0015 V
+/- .05V
5-14 V
.0038 V
+/- .14V
14-30 V
.0081 V
+/- .30V
30-70 V
.0182 V
+/- .70V
70-90 V
.0231 V
+/- .90V
Analog step sizes
Summary of Contents for D-PK-NG216
Page 13: ...9 Fig 4 2 Fig 4 3...
Page 18: ...14 Fig 5 7 Amphenol connector pinout...
Page 20: ...16 Fig 5 9 Optional 66 block connector pinout for controls...
Page 40: ...36 Fig 10 3...
Page 43: ...39 Fig 10 8...
Page 88: ...84...
Page 98: ......