Note
: If the voltage does not read between -36 VDC and -72 VDC, stop immediately.
8. Insert the local fuse into the power fuse slot. The power plug can be inserted into the power
connector only one way to ensure the correct polarity.
Note
: The negative voltage terminal is on the left and the GND terminal is on the right.
9. Verify that the
LED is lit. To confirm that power is correctly connected, the front panel status LED
will flash RED and GREEN, indicating that the firmware is booting up.