background image

English

10

 – English

1 2

3

4

5

25

6

B

C

A

D

E

F

–––  STEP 6  –––

6.1 - INSTALL AND CONNECT PH100 PHOTOCELLS (fig. 25)

Caution:

 disconnect the power supply to the system before performing 

any installation operations; if the system is equipped with a PR1 buffer 

battery, the latter must be disconnected.

Warnings: 

Be careful not to damage the oring (

fig. 25-3

[A]

.

Choose the positioning of the two elements that make up the photocell 

(TX and RX) respecting the following requirements:

• Place them at a height of 40-60 cm above ground, at the sides of the 

area to be protected, and as close as possible to the gate wire (no fur-

ther than 15 cm).

• Ducting for passage of the cables must be provided at the intended 

point.

• Point the TX transmitter towards the RX receiver, with a maximum mis-

alignment of 5°.

01.

  Remove the front glass (

fig. 25-1

).

02.

  Position the photocell at the point where the cable passage ducting 

starts.

03.

  Mark the drilling points using the bottom as a reference. Drill the 

holes in the wall using a hammer drill fitted with a 5mm bit and insert 

the 5 mm screw anchors.

04.

  To pass the electrical cables through holes (made as desired): see 

fig. 25-2

.

05.

  Secure the bottom with the relative screws 

[B]

 in 

fig. 25-3

 doing 

so in such a way that the hole on the bottom 

[C]

 in 

fig. 25-3

 corre-

sponds to the cables output. 2 self-tapping screws are also provided 

for fixing on surfaces of different densities.

06.

  Connect the electric cable to the correct terminals, TX and RX (

fig. 

25-4

). From an electrical point of view, TX and RX are connected in 

parallel to one another (

fig. 25-5

) and to the blue terminal on the 

control card. You do not need to observe any polarity.

07.

  Affix the housing cover 

[D]

 in 

fig. 25-6

 with the two screws 

[E]

 in 

fig. 

25-6

 and a Phillips screwdriver. Finally insert the outer cover 

[F]

 in 

fig. 25-6

 closing it with slight pressure.

6.2 -  INSTALL AND CONNECT FL100 FLASHING INDICA-

TOR (fig. 26)

Choose the location of the flashing indicator, so that it is in the vicinity of 

the gate and easily visible. This may be secured to a horizontal or vertical 

surface; 

fig. 26

 shows the two situations:

01.

  Remove the cover, by unscrewing the screw;

02.

  Divide the bottom, unscrewing the screws that are used to allow the 

electrical cables to pass;

03.

  Mark the drilling points using the bottom as a reference, and doing 

it so that the hole at the bottom corresponds to the cables output: 

vertical fixing (

A

) or horizontal fixing (

B

);

04.

  Drill the holes in the wall using a hammer drill fitted with a 6 mm bit 

and insert the 6 mm screw anchors;

05.

  Secure the bottom with the screws;

06.

  Connect the electrical cables in the relevant FLASH and “antenna” 

terminals as shown in the figure: to facilitate the work you can remove 

the terminals, make the connections and then reinsert them.

 

In the FLASH terminal is not necessary to comply with any polarity; 

while in the connection of the shielded antenna cable, connect the 

sock;

07.

  Put the lamp door in the base taking care to push it down so that it 

locks;

08.

  Join the body of the flashing indicator to the mounting bracket and 

turn to the left until you hear a click, and secure with the screw.

Summary of Contents for WS200S

Page 1: ...Instructions and Warnings for Installation and Use WS200S...

Page 2: ...L100 FLASHING INDICATOR 10 PROGRAMMING STEP 7 12 7 1 POWER SUPPLY CONNECTION 12 7 2 PRELIMINARY CHECKS 12 7 3 CONNECTED DEVICES RECOGNITION 12 7 4 GATE LEAF OPEN AND CLOSURE ANGLES RECOGNITION 12 7 5...

Page 3: ...ct must be performed exclusively by a qualified and skilled technician However all preliminary set up installation connection of devices to one another and programming operations may be performed by p...

Page 4: ...h both the data in this paragraph and the technical data in the chapter Product technical speci fications 1 Check that the gate leaf has dimensions and weight which fall within the following limits ma...

Page 5: ...unt that due to possible deposits of water in the routing ducts the ducting might create con densation in the control unit with consequent damage to the electronic circuits Place the ends of the ducti...

Page 6: ...C D D E F a d g d e f b b c 1 3 5 English English 5 A B F 2 G D F C 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 0 20 40 60 80 100 120 140 160 180 200 220 240 90 95...

Page 7: ...using just a slight movement move the gate leaf a few centimetres in the direction of full opening until you hear a click 14 If the gate to be automated is a dual leaf type repeat the same operations...

Page 8: ...English 7 English E B A 6 Distance E minimum 400 mm 8 9 M8 V6 x 70 M6 10 11 12 13 7...

Page 9: ...8 English OK b c d a Maximum 14 14 15 16 17 18 19 21 20 M8 M8 M8 M8...

Page 10: ...English 9 English OPEN STOP TX RX HS100 PH100 FL100 WK100SK M1 WS100SCK ECS bus ECS FLASH bus M M M M Blue Yellow Green Brown B A 22 23 WS100SCK M2 WS100SK M1 24 Brown Yellow Green Blue...

Page 11: ...ig 25 4 From an electrical point of view TX and RX are connected in parallel to one another fig 25 5 and to the blue terminal on the control card You do not need to observe any polarity 07 Affix the h...

Page 12: ...English English 11 26 A B 6 mm x4 6 mm x4 A B A B A B A A A A B B B 1 2 3 4 4 A B A B A B A B A B A B 5 6 7 8 9 11 12 10 A B A B...

Page 13: ...e P2 LED flashes it means that an error has occurred see section 10 5 Troubleshooting The phase of self learning the devices connected can be repeated at any time also after installation such as in th...

Page 14: ...ed according to the risks present and for ensuring observance of all legal provisions standards and regulations and in particular all requirements of the standard EN 12445 which establishes the test m...

Page 15: ...ter to change T1 T2 STEP 9 The maintenance operations must be performed in strict com pliance with the safety directions provided in this manual and according to the applicable legislation and standar...

Page 16: ...imes Motor 1 and Motor 2 discharge in closure 1 No discharge Press T3 once 2 0 1s Minimum Press T3 twice 3 0 2s Press T3 three times 4 0 3s Press T3 four times 5 0 4s Medium Press T3 five times 6 0 5s...

Page 17: ...ch which allows you after having correctly entered the secret combination to control the automation remotely For programming see paragraph 10 4 6 10 2 1 Installing the PR3 buffer battery fig 33 CAUTIO...

Page 18: ...e Ea 14 Am 200 thus Ed 2800 Establish the energy consumed To calculate the energy consumed by the automation proceed as follows 05 In the table below choose the box corresponding to the intersection o...

Page 19: ...during the self learning phase after which a STOP command is activated whenever a variation with respect to the learned status is detected 10 3 3 Recognition of Other Devices Normally the recognition...

Page 20: ...llowing paragraphs before you proceed with their execution 10 4 1 Mode 1 memorisation 01 Press P1 fig 35 for at least 3 s When the LED P1 lights up release the key 02 Within 10s press any key on the r...

Page 21: ...pressed repeat step 3 within another 10 seconds otherwise the deletion phase will stop automatically English 20 English 10 4 5 Deleting all memorised radio transmitters This operation deletes all memo...

Page 22: ...inter mittent the voltage value is not important approximately 10 30 Vac if there is voltage the problem is due to the lamp in this case replace the lamp with one having the same characteristics TABLE...

Page 23: ...egular operation and when there is a problem see Table 13 Quick flashes 1 flash 1 second pause 1 flash 2 flashes 1 second pause 2 flashes 3 flashes 1 second pause 3 flashes 4 flashes 1 second pause 4...

Page 24: ...ognition phase in progress Action Cycle operation Complete cycle operation Carry out the recognition phase see chapter 3 5 2 Leaf open and closure angles recognition Indicates that the open angles sel...

Page 25: ...bly shorter than 5m observe the warnings regarding minimum gauge and type of cables Ambient operating temperature 20 50 C Use in acid saline or potentially explosive atmospheres NO Mounting On a horiz...

Page 26: ...th Addressing capability Ambient operating temperature Use in acid saline or potentially explosive atmospheres Mounting Protection rating Dimensions weight Presence detector for automation of automati...

Page 27: ...utomatic gates and doors AM OOK radio encoded modulation 433 92 MHz Rolling code with 64 Bit code 18 billion billion combinations 4 each key can be used for the various control unit commands or to com...

Page 28: ...PH100 and FL100 conform to DIRECTIVE 2004 108 EC OF THE EUROPEAN PARLIAMENT AND COUNCIL of December 15 2004 concerning alignment of Member States legislation regarding electromagnetic compat ibility...

Page 29: ...ready ready for use and the four keys have the following functions fig 42 This table must be compiled by the person who programmed the automation Function T1 Key T2 Key T3 Key T4 Key Action Rotated to...

Page 30: ...ing leaves and stones to ensure that noone can operate the door Check the system periodically in particular all cables springs and supports to detect possible imbalance signs of wear or damage Do not...

Page 31: ......

Reviews: