Example: to adjust the pause time to 40 s.

01.

  Press the T1 and T2 keys and hold them down for at least 5s

02.

  Release T1 and T2

03.

  Press T1 three times

All the parameters can be adjusted as required without any contraindica-

tion; only the adjustment of the “motor force” could require special care:

• Do not use high force values to compensate for the fact that the gate 

has anomalous friction points. Excessive force can be detrimental to the 

functioning of the safety system or can damage the gate. 

• If the “Motor force control” is used in support of the system for impact 

force reduction, the force measurement procedure must be performed 

after each adjustment, as envisaged by standard EN 12445.

•  Weather conditions may affect the movement of the gate. Periodically 

you may need to readjust.

To program the parameters in Table 4:

01.

  Press T1 and T3 together (

fig. 32

) on the radio transmitter for at least 

5 s.

02.

  Release the two keys.

03.

  Within three seconds, carry out the action set out in Table 4 based on 

the parameter to change.

32

TABLE 4

Parameters

N° Value

Action to perform

Open input configuration on the control unit

1

Open (*)

Press T1 once

2

pedestrian opening

Press T1 twice

Flash output configuration

1

Flashing light (*)

Press T2 once

2

Courtesy light

Press T2 twice

3

Gate open indicator

Press T2 three times

Motor 1 and Motor 2 discharge in closure

1

No discharge (*)

Press T3 once

2

0.1s (Minimum)

Press T3 twice

3

0.2s

Press T3 three times

4

0.3s

Press T3 four times

5

0.4s (Medium)

Press T3 five times

6

0.5s

Press T3 six times

7

0.6s

Press T3 seven times

8

0.7s (Maximum)

Press T3 eight times

Motor 1 and Motor 2 discharge in opening

1

No discharge (*)

Press T4 once

2

0.1s (Minimum)

Press T4 twice

3

0.2s

Press T4 three times

4

0.3s

Press T4 four times

5

0.4s (Medium)

Press T4 five times

6

0.5s

Press T4 six times

7

0.6s

Press T4 seven times

8

0.7s (Maximum)

Press T4 eight times

(*) 

Original factory value

Example: to adjust the closing discharge of motors 1 and 2 to level 4.

01.

  Press the T1 and T3 keys and hold them down for at least 5s

02.

  Release T1 and T3

03.

  Press T3 four times

Parameters 

Pause time

Pedestrian opening

Motor force

“OPEN” function

1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4

Action: 

operation to be carried out at step 3 in the 

recognition phase

Press T1 once
Press T1 twice
Press T1 three times
Press T1 four times
Press T2 once
Press T2 twice
Press T2 three times
Press T2 four times
Press T3 once
Press T3 twice
Press T3 three times
Press T3 four times
Press T4 once
Press T4 twice
Press T4 three times
Press T4 four times

TABLE 3

Value

10s
20s (*)
40s
80s
Open 1 leaf halfway
Fully open 1 leaf (*)
2 leaves partially opened to 1/4 of the full course
2 leaves partially opened to half of the full course
Low 
Medium low (*)
Medium high
High 
“Open”, “Stop”, “Close”, “Stop”
“Open”, “Stop”, “Close”, “Open” (*)
“Open”, “Close”, “Open”, “Close”
Open only

(*) 

Original factory value

Summary of Contents for WS200S

Page 1: ...Instructions and Warnings for Installation and Use WS200S...

Page 2: ...L100 FLASHING INDICATOR 10 PROGRAMMING STEP 7 12 7 1 POWER SUPPLY CONNECTION 12 7 2 PRELIMINARY CHECKS 12 7 3 CONNECTED DEVICES RECOGNITION 12 7 4 GATE LEAF OPEN AND CLOSURE ANGLES RECOGNITION 12 7 5...

Page 3: ...ct must be performed exclusively by a qualified and skilled technician However all preliminary set up installation connection of devices to one another and programming operations may be performed by p...

Page 4: ...h both the data in this paragraph and the technical data in the chapter Product technical speci fications 1 Check that the gate leaf has dimensions and weight which fall within the following limits ma...

Page 5: ...unt that due to possible deposits of water in the routing ducts the ducting might create con densation in the control unit with consequent damage to the electronic circuits Place the ends of the ducti...

Page 6: ...C D D E F a d g d e f b b c 1 3 5 English English 5 A B F 2 G D F C 110 120 130 140 150 160 170 180 190 200 210 220 230 240 250 260 270 280 290 300 0 20 40 60 80 100 120 140 160 180 200 220 240 90 95...

Page 7: ...using just a slight movement move the gate leaf a few centimetres in the direction of full opening until you hear a click 14 If the gate to be automated is a dual leaf type repeat the same operations...

Page 8: ...English 7 English E B A 6 Distance E minimum 400 mm 8 9 M8 V6 x 70 M6 10 11 12 13 7...

Page 9: ...8 English OK b c d a Maximum 14 14 15 16 17 18 19 21 20 M8 M8 M8 M8...

Page 10: ...English 9 English OPEN STOP TX RX HS100 PH100 FL100 WK100SK M1 WS100SCK ECS bus ECS FLASH bus M M M M Blue Yellow Green Brown B A 22 23 WS100SCK M2 WS100SK M1 24 Brown Yellow Green Blue...

Page 11: ...ig 25 4 From an electrical point of view TX and RX are connected in parallel to one another fig 25 5 and to the blue terminal on the control card You do not need to observe any polarity 07 Affix the h...

Page 12: ...English English 11 26 A B 6 mm x4 6 mm x4 A B A B A B A A A A B B B 1 2 3 4 4 A B A B A B A B A B A B 5 6 7 8 9 11 12 10 A B A B...

Page 13: ...e P2 LED flashes it means that an error has occurred see section 10 5 Troubleshooting The phase of self learning the devices connected can be repeated at any time also after installation such as in th...

Page 14: ...ed according to the risks present and for ensuring observance of all legal provisions standards and regulations and in particular all requirements of the standard EN 12445 which establishes the test m...

Page 15: ...ter to change T1 T2 STEP 9 The maintenance operations must be performed in strict com pliance with the safety directions provided in this manual and according to the applicable legislation and standar...

Page 16: ...imes Motor 1 and Motor 2 discharge in closure 1 No discharge Press T3 once 2 0 1s Minimum Press T3 twice 3 0 2s Press T3 three times 4 0 3s Press T3 four times 5 0 4s Medium Press T3 five times 6 0 5s...

Page 17: ...ch which allows you after having correctly entered the secret combination to control the automation remotely For programming see paragraph 10 4 6 10 2 1 Installing the PR3 buffer battery fig 33 CAUTIO...

Page 18: ...e Ea 14 Am 200 thus Ed 2800 Establish the energy consumed To calculate the energy consumed by the automation proceed as follows 05 In the table below choose the box corresponding to the intersection o...

Page 19: ...during the self learning phase after which a STOP command is activated whenever a variation with respect to the learned status is detected 10 3 3 Recognition of Other Devices Normally the recognition...

Page 20: ...llowing paragraphs before you proceed with their execution 10 4 1 Mode 1 memorisation 01 Press P1 fig 35 for at least 3 s When the LED P1 lights up release the key 02 Within 10s press any key on the r...

Page 21: ...pressed repeat step 3 within another 10 seconds otherwise the deletion phase will stop automatically English 20 English 10 4 5 Deleting all memorised radio transmitters This operation deletes all memo...

Page 22: ...inter mittent the voltage value is not important approximately 10 30 Vac if there is voltage the problem is due to the lamp in this case replace the lamp with one having the same characteristics TABLE...

Page 23: ...egular operation and when there is a problem see Table 13 Quick flashes 1 flash 1 second pause 1 flash 2 flashes 1 second pause 2 flashes 3 flashes 1 second pause 3 flashes 4 flashes 1 second pause 4...

Page 24: ...ognition phase in progress Action Cycle operation Complete cycle operation Carry out the recognition phase see chapter 3 5 2 Leaf open and closure angles recognition Indicates that the open angles sel...

Page 25: ...bly shorter than 5m observe the warnings regarding minimum gauge and type of cables Ambient operating temperature 20 50 C Use in acid saline or potentially explosive atmospheres NO Mounting On a horiz...

Page 26: ...th Addressing capability Ambient operating temperature Use in acid saline or potentially explosive atmospheres Mounting Protection rating Dimensions weight Presence detector for automation of automati...

Page 27: ...utomatic gates and doors AM OOK radio encoded modulation 433 92 MHz Rolling code with 64 Bit code 18 billion billion combinations 4 each key can be used for the various control unit commands or to com...

Page 28: ...PH100 and FL100 conform to DIRECTIVE 2004 108 EC OF THE EUROPEAN PARLIAMENT AND COUNCIL of December 15 2004 concerning alignment of Member States legislation regarding electromagnetic compat ibility...

Page 29: ...ready ready for use and the four keys have the following functions fig 42 This table must be compiled by the person who programmed the automation Function T1 Key T2 Key T3 Key T4 Key Action Rotated to...

Page 30: ...ing leaves and stones to ensure that noone can operate the door Check the system periodically in particular all cables springs and supports to detect possible imbalance signs of wear or damage Do not...

Page 31: ......

Reviews: