11 Other System Parameters
11.1 VSmart Module Petro-
Net™ Addressing
VSmart Modules and I/O Modules must each be assigned a unique
identification number. Module numbers must be unique within the
Module Group
; that is, you can assign the same number to both a
VSmart Module and to an I/O Module, but you
cannot
assign the same
number to more than one VSmart Module or to more than one I/O
Module. The module numbers are used when the system is
configured. Refer to your
SiteSentinel® iSite™ Configuration Manual
for details about system setup.
A small, red rotary switch is located at the top of the PC board inside
each module. The switch has 10 positions, marked “0” to “9.” A small
arrow on the switch points to the current position. Default switch
setting is
“1.”
Although the switch has 10 settings, only settings 1-8 are valid. DO
NOT set the
switch to either “0” or “9” – the module will NOT be
recognized by the system!
Follow these steps to set the Petro-
Net™ Address:
1. Turn the module power OFF.
2. Use a ¼-inch (6 mm) blade screwdriver to gently rotate
the small white screw inside the rotary switch to the
desired location.
3. Turn the module power to ON.
DO NOT change the module number while the module power is ON.
The eight-position dipswitch should remain in the closed position for
normal operation.
Summary of Contents for OPW SiteSentinel iSite
Page 15: ...Page 15 of 145 www opwglobal com Figure 2 4 Console Connectivity ...
Page 17: ...Page 17 of 145 www opwglobal com Figure 2 6 Wiring Connections ...
Page 22: ...Page 22 of 145 www opwglobal com Figure 2 11 Standard Twisted Pair Petro Net Installation ...
Page 25: ...Page 25 of 145 www opwglobal com Figure 2 14 Petro Net Over Ethernet Option ...
Page 33: ...Page 33 of 145 www opwglobal com ...
Page 34: ...Page 34 of 145 www opwglobal com Figure 4 1 924B Probe Installation ...
Page 61: ...Page 61 of 145 www opwglobal com Figure 5 22 In Tank Probe Setup ...
Page 74: ...Page 74 of 145 www opwglobal com Figure 9 3 Dry Well Monitoring Single Wall Tank ...
Page 78: ...Page 78 of 145 www opwglobal com Figure 9 7 Double Wall Tank with Well Monitoring ...
Page 90: ...Page 90 of 145 www opwglobal com Figure 13 7 ACR RIM Jumper Board ...
Page 142: ...Page 142 of 145 www opwglobal com Declaration of Conformity ...
Page 143: ...Page 143 of 145 www opwglobal com ...