Page 13 of 145
2.2.2 Direct Connections
To establish a direct, wired connection between the SiteSentinel®
iSite™ Console and a PC, a CAT5 crossover cable is required. Follow
these steps to connect:
1.
Connect one end of the CAT5 crossover cable to the console’s
Ethernet port, and the other end to an available Ethernet port on
the PC.
2.
Wait for an “Automatic Private Address” to be assigned to each
Ethernet connection by its respective system (this occurs
automatically when a DHCP server is unavailable).
3.
Navigate to the
Networking
section of the
System Settings
menu on the console and check the DHCP configuration. Then
select “Renew IP” to renew the console’s IP Address (Figure 2-
3).
“Automatic Private Addresses” will always take the form
169.254.xxx.yyy, where “xxx” and “yyy” may be any numeric value
between 1 and 254; specific values will not affect the availability of a
connection.
4.
Once established, enter the SiteSentinel® iSite™ console’s
network IP address as displayed on the \System\Network view
into the address bar of the PC’s Web browser. The console’s
screen view will be displayed.
PC network settings may need to be adjusted to establish a direct
connection. A machine that is set up for static IP connections will
either need to be changed to DHCP or have its IP address set one
number higher or low
er than the console’s IP address in order to
connect.
Figure 2-3 Direct Connection Screen
Summary of Contents for OPW SiteSentinel iSite
Page 15: ...Page 15 of 145 www opwglobal com Figure 2 4 Console Connectivity ...
Page 17: ...Page 17 of 145 www opwglobal com Figure 2 6 Wiring Connections ...
Page 22: ...Page 22 of 145 www opwglobal com Figure 2 11 Standard Twisted Pair Petro Net Installation ...
Page 25: ...Page 25 of 145 www opwglobal com Figure 2 14 Petro Net Over Ethernet Option ...
Page 33: ...Page 33 of 145 www opwglobal com ...
Page 34: ...Page 34 of 145 www opwglobal com Figure 4 1 924B Probe Installation ...
Page 61: ...Page 61 of 145 www opwglobal com Figure 5 22 In Tank Probe Setup ...
Page 74: ...Page 74 of 145 www opwglobal com Figure 9 3 Dry Well Monitoring Single Wall Tank ...
Page 78: ...Page 78 of 145 www opwglobal com Figure 9 7 Double Wall Tank with Well Monitoring ...
Page 90: ...Page 90 of 145 www opwglobal com Figure 13 7 ACR RIM Jumper Board ...
Page 142: ...Page 142 of 145 www opwglobal com Declaration of Conformity ...
Page 143: ...Page 143 of 145 www opwglobal com ...