5.4 Single-Level Sump Sensor
Part No. 30-0231-L
The Single-Level Sump Sensor
(
Figure 5-4
)
is designed to detect the
presence of liquid in sumps, dispenser pans and other locations where
the presence of a liquid could indicate that a leak has occurred.
The sensor contains a normally closed float switch that activates in the
presence of liquid. In the event of a break in the cable, the system will
activate the alarm.
Maximum Wiring Length is the maximum length of cable to be used to
connect all sensors on an individual channel. This length includes run
of cable from VSmart to each sensor board in the string.
5.4.1 Installation
1. Check that the sump is dry.
2. Position the sensor on the bottom of the sump/pan and
secure the sensor wire to an existing pipe or bracket with a
tie wrap.
3. Connect the sensor wires to the field wires in the junction
box using the supplied wire nuts.
4. Seal the electrical connections with the epoxy seal packs.
Figure 5-4 Single-Level Sump Sensor
Single level Sump Sensor Specifications
Detects:
Liquid
Cable Requirements:
Belden #88760 or Alpha #55371
Operating Temperature:
-40°F to 158°F (-40°C to +70°C)
Dimensions:
Length: 3.75” (9.5 cm), Diameter: 2.9” (7.4 cm)
Maximum Wiring Length*:
1,000’ (305 m) field wiring
Multi-Drop Restriction:
16 per I.S. barrier channel (64 per barrier)
Connections:
Red = Power, Black = Signal, Shield = Ground
Summary of Contents for OPW SiteSentinel iSite
Page 15: ...Page 15 of 145 www opwglobal com Figure 2 4 Console Connectivity ...
Page 17: ...Page 17 of 145 www opwglobal com Figure 2 6 Wiring Connections ...
Page 22: ...Page 22 of 145 www opwglobal com Figure 2 11 Standard Twisted Pair Petro Net Installation ...
Page 25: ...Page 25 of 145 www opwglobal com Figure 2 14 Petro Net Over Ethernet Option ...
Page 33: ...Page 33 of 145 www opwglobal com ...
Page 34: ...Page 34 of 145 www opwglobal com Figure 4 1 924B Probe Installation ...
Page 61: ...Page 61 of 145 www opwglobal com Figure 5 22 In Tank Probe Setup ...
Page 74: ...Page 74 of 145 www opwglobal com Figure 9 3 Dry Well Monitoring Single Wall Tank ...
Page 78: ...Page 78 of 145 www opwglobal com Figure 9 7 Double Wall Tank with Well Monitoring ...
Page 90: ...Page 90 of 145 www opwglobal com Figure 13 7 ACR RIM Jumper Board ...
Page 142: ...Page 142 of 145 www opwglobal com Declaration of Conformity ...
Page 143: ...Page 143 of 145 www opwglobal com ...