l
Calibration cycles max
: This is the maximum calibration cycles value parameter. This sets the
number of auto calibration cycles in which the segments will not be changed if the auto calibration
process is not complete. the minimum value is 5 and the maximum is 10.
l
Calibration cycles required
: This value specifies the Autocalibration status percentage (%).
When each segment of the specified auto calibration volume range is at this value, Autocalibration is
complete. Because there can be segments in an Autocalibration cycle that are not changed, some
segments can be changed more than the required value.
6.3.7 ACR Results
6.3.8 Reconciliation
l
Test vend
: This is the quantity of product used in the calibration of hose meters. In meter calibration,
there is a product quantity removed from the tank without a related sale. if
Unaccounted variance
is
greater than Test vend threshold, then it is reported as “Test vend” and it is not thought of as a “Loss”.
l
Unexpected sales (liters)
: An alarm will be caused when the tank is in a quiet mode (there are no
sales) and product loss is sensed.
l
Average time
: This specifies the time for the loss warning or loss alarm.
l
Loss warning (liters)
: A difference more than this threshold will cause a Loss Warning
M2051-EU Rev.: 1 Dover Fueling Solutions