6.3.2 Thresholds
1. Select
Thresholds
from the configurations parameters. Use one of two methods to adjust each of
the parameter values:
a. Move the slider until you get the correct values.
i.
The slider for
Safe working capacity
adjusts by
%
. The Level and Volume
values will adjust automatically.
ii.
The slider for all other parameters adjusts by
Level
. The Volume and % values
will adjust automatically.
b. Click the
Edit
icon
for one of the values. Enter the correct value in the pop-up. Click
OK
to save the value. The other values for that parameter will adjust automatically.
2. Click
Save
when you complete the
Thresholds
configuration.
NOTE:
.From the top Threshold down, each of the Threshold value sets (Level, Volume and
%) must be lower than the one above it. For example, the Low Threshold must have lower
values than the High Threshold. If the values are not set correctly, the SAVE button will not be
on.
M2051-EU Rev.: 1 Dover Fueling Solutions
Page 33