1. Using the button
open the “Parameter
management” menu.
2. Using the button
Switch to “Production”
menu.
Fig. 60: Production
1 Current process values
2 Setting the process parameter(s)
3 Setting PID parameter(s)
Process parameter
– User level 2 required.
PID parameter
– User level 3 required
Fig. 61: Setting parameters
3. Tap the field (1) behind the required parameter.
4. Enter and confirm parameter.
8.7.3 Standby
Process parameter
Rotational speed [Hz]
Rotational speed of the motor in Stand-by
mode. Values between 10 and 80 Hz can be
parameterized.
Control pressure recirculation controller [bar]
Set control pressure for the recirculation
controller in stand-by mode. Values between
0 and 5 bar can be parameterized.
Interval mode.
Operating the pump at intervals. The oper-
ating time and idle time are available as
parameters.
Operating time
Details of the pump interval Values between
5 and 999 min can be parameterized.
Idle period
Details of the pump down time. Values
between 5 and 999 min can be parameter-
ized.
Setting parameters
Personnel:
System operator
1. Open the “Parameter management” menu
using the
button.
2. Switch to “Standby” menu using the button
.
Fig. 62: Standby
1 Setting the process parameter(s)
2 Display of the current process values
Visualizer
05/2017
EcoPUC MC - MCU00003EN
33/68