dormakaba ED50 OHC Installation Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Power assist function (v1.7)
1. Force setting for Power assist function.
2. Power assist function only available with
hd
parameter = 1, manual mode.
3. "0"; power assist function OFF; power assist function enabled for available values
greater than 0.
4. Power assist function enabled when power assist activation angle
hA
reached.
5. The greater the value of
hF
, the easier the door can be manually opened from power
assist activation angle
hA
.
6. If power assist set too high, door can open automatically.
7. Power assist function is not available
• If operator is switched off
• A smoke detector or emergency button has been triggered.
36
0 - 10
0
Power assist function support for manual
mode in door closed position (v1.9)
1. Setting for power assist function support with door in
closed
position.
2. Power assist function only available with
hd
parameter = 1, manual mode.
3. The greater the value of
hS
, the easier the door can be manually opened from the
closed
position.
37
0 - 10
0
hS
F1 , F3-F8 Upgrade card parameter values
F2, ED50 full/low energy mode
0 - 3
0
0
Upgrade card not installed, function not available.
1
Upgrade card installed, function not activated.
2
Upgrade card installed, function activated.
3
Upgrade card has been removed, function no longer available.
Upgrade card, fire protection
1. Once upgrade card installed, parameter value will automatically change to 2.
2. Following activation, drive may be used as a electrically controlled hold-open system
according to EN 14637, Building hardware-Electrically controlled hold-open systems for
fire/smoke door assemblies, or similar standards.
3. Full energy function is automatically activated.
4. Plug for terminal board X9 socket included with upgrade card.
38
0, 2, 3
0
This paragraph left intentionally blank.
39
Upgrade card professional, impulse relay
1. Once upgrade card installed, parameter value will automatically change to 1.
2. Function must be activated by changing parameter
F3
to 2.
3. Door can be controlled with a pushbutton connected to Night-bank input without a
door hold open time:
• Door opens with first pulse and remains open. The hold open time is not limited.
• Door closes only with second pulse of pushbutton.
4. Pushbutton in 3. must be connected to terminal board Night-bank input:
• X1, 3 and 35 (dry)
• X10, 57 and 57a (wet)
5. Standard hold-open time
dd
is available when door is opened using other internal and
external detectors.
40
0, 1,
2, 3
0