dormakaba ED50 OHC Installation Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Status relay function, X7 terminals
0
Status relay is deactivated.
27
0 - 6
1
1
Status relay activated as soon as door reaches door "closed" position.
2
Status relay activated as soon as door reaches door "open" position.
3
Status relay activated when error codes are displayed on 2 digit operator display.
4
"Door closed and locked" activates status relay.
5
Status relay activated when information or error codes are displayed on 2 digit
operator display (v1.9).
6
1. Status relay activated when door is opened further than opening angle
parameter
OA
, set during learning cycle.
2. Parameter
OA
value can only be changed using dormakaba handheld or by
performing another learning cycle.
Locking device output configuration;
output X3, 1G (24V) and input X6, 4/4a
Reference Chapter 7
28
0 - 1
0
0
Locking device output terminal X3, 1G (24V) is independent of Input X6, 4/4a.
1
1. Locking device output terminal X3, 1G (24V) is turned on as soon as contact at
X6, 4/4a is opened (
v1.9
).
2. Terminal X3, 1G 24V output is on for as long as contact at X6, 4/4a is open,
motor lock with a 100% duty factor is required.
3. This function is not available for DCW®- motor locks.
Cycle counter
1. Total number of opening and closing cycles displayed is shown in increments of 10000.
• Display value, "4", 40,000 cycles.
• Display value, "53", 530,000 cycles.
2. Total number of cycles can be displayed on dormakaba handheld.
3. A display value of "99" means 990,000 cycles or greater.
29
0 - 99
* 10000
cycles
Delete error log
30
0 - 1
0
0
No function.
1
1. When "1" entered, Error log is deleted.
2. Parameter is then automatically reset to "0".
Reset service interval display,
operator yellow LED
31
0 - 1
0
0
No function.
1
1. When "1" entered:
• Service cycle counter is reset to 200,000.
• Service interval is reset to 12 months.
• Yellow LED not illuminated.
2. Parameter is then automatically reset to "0".
3. Values other than default values must be set using dormakaba handheld:
• Maintenance interval
• Maintenance cycles