102
ED50
08-2018
DL4614-140
dormakaba ED50 OHC Installation Instructions
Appendix A
Parameter
Value
range
Units
Factory
setting Description
Power reserve module SVP-PR 12 test
16
0 - 1
0
0
Test off
1
1. SVP-PR 12 power reserve module test is performed once every 24 hours, or
10 minutes after AC power has been turned on. In event of an error:
• Unlocking is not performed and no automatic door movements are initiated.
• Error code
E 25
is displayed, See Appendix B4, Troubleshooting Error Codes.
2. SVP-PR 12 power reserve module can be used but must be tested on a regular
basis if using:
• SVP-2000 DCW® emergency escape motor lock with automatic latching action.
• M-SVP 2000 DCW® emergency escape lock, v1.5 or later.
3. Test is automatically activated if a fire protection module is recognized in
conjunction with SVP-2000 DCW® or M-SVP 2000 DCW® locks.
TS
Static force in opening direction
1. Static force in opening direction (basic parameter for wind load control). Static force
on door closing edge can be changed using this parameter.
2. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standards A156.10 (full energy)
or A156.19 (low energy) standards. See Chapter 36.
*Static force range is reduced with Low Energy mode. See Chapter 36.
17
2- 15
*10
N
6
*10
.45- 3.4
*10
lbf
1.35
*10
Static force in closing direction
1. Static force in closing direction (basic parameter for wind load control). Static force on
door closing edge can be changed using this parameter.
2. Internal monitoring system checks if parameter setting is admissible. If setting exceeds
admissible value, the setting is alternately displayed with the permissible value.
3. After parameter set, verify setting meets ANSI/BHMA standards A156.10 (full energy)
or A156.19 (low energy) standards. See Chapter 36.
*Static force range is reduced with Low Energy mode. See Chapter 36.
18
2- 15
*10
N
6
*10
.45- 3.4
*10
lbf
1.35
*10
Motor driven latching action, automatic
mode
1. System offers a motor driven latching action in automatic mode in addition to
mechanical latching action.
2. The
EP
parameter setting (v1.7) is designed to increase static force on door to insure
proper closing despite resistance caused by door seals or locking devices.
3. Setting should be increased step by step from a low setting so as to avoid damage to
the system. Use the lowest possible setting.
4. Ensure that both the door itself and the arm or track installation are suitable for the
additional, permanent forces.
19
0 - 9
0
Motor driven latching action angle (v1.7)
Door opening angle at which motor driven latching action
EP
is activated.
• Starting angle of the latching angle adjustable from 10°. (v1.7).
20
2 -10
°
3
Keep closed force
21
0 - 9
0
0
Off
1
to
9
1. Keep closed force is:
• Permanently applied following motor drive latching action.
• Designed to keep door in closed position even if wind acts on door.
2. Keep closed force can be set from 0 (off) to 9, maximum force.