25
G60, G80, G100, G150, G200-SIIIA OM Manual
STARTING
CAUTION
Use the EMERGENCY STOP button ONLY in the
event of an emergency.
NEVER use it for normal shut-down.
Verify the following:
1.
All external electrical power loads are turned “OFF”.
2.
Main Breaker is “OFF”.
3.
Battery Disconnected Switch is “ON”.
4.
Reset (pull to unlatch) Emergency Stop Button.
5.
Push the controller “START” Button.
6.
Wait for preheating if enabled.
CAUTION
Do NOT use engine starting fluids.
DANGER
POWER is present upon cranking the engine.
CAUTION
Allow starter to cool for one minute between start
attempts.
If engine shuts down, diagnostic lamps will indicate
the problem. Correct the problem before continuing.
7.
Allow the engine to warm-up for 3 to 5 minutes.
8.
Check the CONTROL Panel for proper voltages. No
RED diagnostic lamps should be glowing.
9.
With main breaker “ON” power is present and
available for use.
10. Close side doors for optimum cooling of the unit while
running.
STOPPING
1.
Turn off all external electrical power loads.
2.
Turn Main Breaker “OFF”.
3.
Allow 5 minute cool down.
4.
Push controller “STOP” Button.
5.
Wait at least 15 seconds before restarting.
6.
Fill fuel tank at end of working day to prevent
condensate.
REMOTE STARTING AND STOPPING
(ANALOG CONTROLLER)
1.
Connect the Remote Start contacts (located in the
Generator System direct hook-up compartment) to a
customer-supplied contact that closes to initiate a
genset start.
2.
Push the Autostart Mode Switch to illuminate the
Autostart Mode LED on control panel.
3.
When the customer contact closes, a 10-second
alarm will sound prior to each crank cycle until the
engine starts. Preheating will also occur if enabled.
4.
The engine will stop when the customer-supplied
contact opens, and the controller will return to Auto
Start Mode.
Figure 1
1.
Autostart connections
Summary of Contents for G06030001
Page 2: ......
Page 4: ...4 G60 G80 G100 G150 G200 SIIIA OM Manual ...
Page 8: ...8 G60 G80 G100 G150 G200 SIIIA OM Manual ...
Page 9: ...9 G60 G80 G100 G150 G200 SIIIA OM Manual ...
Page 10: ...10 G60 G80 G100 G150 G200 SIIIA OM Manual ...
Page 14: ...14 G60 G80 G100 G150 G200 SIIIA OM Manual ...
Page 89: ......
Page 90: ......