BIOCLASS iC DX
14
BOILER'S SETUP PARAMETERS
The following parameters in the "
Technical Menu
" allow to adjust the boiler to each installation. They only
may be modified by a person with sufficient technical knowledge of the meaning of each parameter. Any
inappropriate setting of a parameter of
“Technical Menu”
can cause a serious malfunctioning of the boiler
and could cause damages to people, animals or things.
14.1
Boiler Model (P.01)
Parameter
P.01
displays the model of the boiler set at DIP-switch on the electronic board.
P.01
= 18 =>
Bioclass iC DX 18
P.01
= 25 =>
Bioclass iC DX 25
14.2
Boiler heat output (P.02, P.03)
Bioclass iC DX
boiler is configured to modulate between a minimum and a maximum burner heat
output. By means of parameters
P.02
and
P.03
the minimum and maximum heat output of the burner
may be set at desired value. The range of modulation selectable depends on the model of boiler and
the type of fuel set.
14.3
General fan speed factor (P.04)
Using parameter
P.04
, a multiplication factor for the fan speed percentage can be set when automatic
fan adjustment is not activated. Using this parameter, the amount of combustion air can be increased
or decreased, to ensure correct combustion values. Changing its value modifies the percentage of the
fan throughout its modulation curve. The selectable range of parameter
P.04
is 0 - 200 (by default
100), if a value lower than 100 is set, the amount of air will be decreased and if a value higher than
100 is set, it will be increased.
14.4
Fuel for ignition (P.05)
By means of parameter
P.05
the amount of fuel for burner ignition procedure may be set at desired
value. The default value depends on the model of boiler and the type of fuel set. The range of values
selectable is 0 - 900 g.
14.5
Fuel consumption (P.06)
By means of parameter
P.06
the amount of fuel consumed by the boiler at 100% heat output may be
set, in kilograms per hour. This parameter is related to the boiler model (heat output) and the type of
fuel used, as well as its calorific value. The range of values selectable is 1.00 - 30.00 kg/h.
14.6
Fuel type (P.07)
By default
Bioclass iC DX
boiler is configured to burn wood pellets. By means of parameter
P.07
another type of fuel may be selected:
P.07
= 0 => Wood pellet.
P.07
= 1 => Olive stone.