BIOCLASS iC DX
12.3
Manual setting of feed auger calibration
By means of this parameter the weight obtained in the feed auger
calibration procedure can be set manually. When
“Manual setting of feed
auger calibration”
parameter is displayed (
) on
"Calibration Menu"
,
press
to access and set the value desired by pressing "
+
" o "
-
" of
DHW
(19)
. The range of values selectable is OFF, 0.500 - 5.000 g.
12.4
Manual ash cleaning activation
By means of this parameter the burner ash cleaning device can be
switched on manually up to a maximum of 20 cleaning cycles. When
“Manual ash cleaning activation”
parameter is displayed (
) on
"Calibration Menu"
, press
to access. SET symbol blinks and
pressing
again it will be activated the cleaning system. A
countdown of 20 cycles will be displayed. When the countdown is
finished the cleaning device will stop. By pressing
the cleaning
procedure can be stopped at any time and by pressing RESET it will
return to
“Calibration Menu”
level.
12.5
Manual circulation pumps activation
By means of this parameter the circulation pumps can be switched on
manually. When
“Manual circulation pump activation”
parameter is
displayed (
) on
"Calibration Menu"
, press
to access. SET symbol
blinks and pressing
again the circulation pumps will be activated for
a period of not more than 20 minutes.
By pressing
the circulation pumps can be stopped at any time and by pressing RESET it will return
to
“Calibration Menu”
level.