3.5 MOUNTING PROCEDURE
To mount the GP-ICR-50 in a wall, the opening behind the wall must be at least 2” (5cm) of depth to allow room for the remote and cable.
1. Cut a 3” x 5” rectangular opening in the wall, ensure there is enough material for the screws to securely mount the remote.
2. Use the GP-ICR-50 as a template for the 4 holes, mark the positions of the 4 holes with a pencil/pen.
3. Drill the 4 pilot holes for the #8 x 3/4” screws.
4. Route one end of the remote control cable through the wall opening to the Inverter / Charger, plug this end into the REMOTE port.
5. Take the other end of the remote cable and plug it into the rear of the GP-ICR-50. The remote should power up if the
Inverter/Charger
is connected to the battery bank. All power to operate the GP-ICR-50 is provided by the
Inverter/Charger
through the remote cable.
6. When the remote powers up, secure the remote control unit to the wall using the four Phillips screws supplied.
Remote Control Port
Remote Cable
Inverter/Charger
Panel /
Wall
Mounting
Screws
(304mm)
12”
(51mm)
2”
(124mm)
4.9”
(124mm)
4.9”
(346mm)
13.6”
(7mm)
(13mm)
.28”
(321mm)
12.6”
.51”
(205mm)
8.1”
(349mm)
13.7”
(378mm)
14.9”
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG
-
POS
+
BATTERY
TEMP
REMOTE
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
REMOTE
BATTERY
TEMP
ON/OFF
STATUS
INV. / CHR.
MODE
AC INPUT
INV. AC
OUTPUT
NEG
-
POS
+
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
CAUTION:
• TO PREVENT FIRE, DO NOT COVER OR OBSTRUCT VENTILATION OPENINGS. DO NOT MOUNT IN ZERO-CLEARANCE
COMPARTMENT. OVERHEATING MAY RESULT. • RISK OF ELECTRIC SHOCK, DO NOT REMOVE COVER, NO USER
SERVICEABLE PARTS INSIDE. REFER SERVICING TO QUALIFIED SERVICE PERSONNEL. • TO REDUCE RISK OF
ELECTRIC SHOCK, DO NOT EXPOSE TO RAIN OR SPRAY. • BATTERY POLARITY MUST BE CORRECT OR DAMAGE WILL
RESULT. • PROVIDED WITH INTEGRAL PROTECTION AGAINST OVERLOADS. • CHARGE ONLY LEAD ACID TYPE
RECHARGEABLE BATTERIES, EACH 6 or 12 CELLS IN THE BATTERY.
MISE EN GARDE:
• POUR PRÉVENIR LES RISQUES D’INCENDIE, NE PAS COUVRIR NI OBSTRUER LES OUVERTURES D’AÉRATION. NE
PAS MONTER LE PRODUIT DANS UN COMPARTIMENT SANS AUCUN DÉGAGEMENT. RISQUE DE SURCHAUFFE. •
RISQUE DE DÉCHARGE ÉLECTRIQUE, NE PAS RETIRER LE COUVERCLE, NE CONTIENT AUCUNE PIÈCE SUSCEPTIBLE
D’ÊTRE RÉPARÉE PAR L’UTILISATEUR. CONFIEZ L’ENTRETIEN À DU PERSONNEL QUALIFIÉ. • POUR RÉDUIRE LES
RISQUES DE DÉCHARGE ÉLECTRIQUE, NE PAS L’EXPOSER À LA PLUIE OU À LA PULVÉRISATION. • L’ORIENTATION
DE LA POLARITÉ DES PILES DOIT ÊTRE CORRECTE, AU RISQUE D’ENDOMMAG ER LE PRODUIT. • FOURNI AVEC UNE
PROTECTION INTÉGRALE CONTRE LA SURCHARGE. • NE CHARGER QUE DES PILES AU PLOMB RECHARGEABLES
CONTENANT CHACUNE 6 ou 12 CELLULES.
WARNING:
• THIS EQUIPMENT EMPLOYS COMPONENTS THAT TEND TO PRODUCE ARCS OR SPARKS. TO PREVENT FIRE OR
EXPLOSION, DO NOT INSTALL IN COMPARTMENTS CONTAINING BATTERIES OR FLAMMABLE MATERIALS. • RISK
OF ELECTRIC SHOCK. USE ONLY THE GROUND-FAULT CIRCUIT-INTERRUPTER RECEPTACLE OR CIRCUIT
BREAKER SPECIFIED IN THE INSTALLATION AND OPERATING INSTRUCTIONS SUPPLIED WITH THIS UNIT. OTHER
TYPES MAY FAIL TO OPERATE PROPERLY WHEN CONNECTED TO THIS UNIT. • RISK OF ELECTRIC SHOCK,
HEATSINKS ARE NOT BONDED TO GROUND, TEST BEFORE TOUCHING. • INTENDED FOR CONTINUOUS DUTY.
AVERTISSEMENT:
• CET ÉQUIPEMENT EMPLOIE DES COMPOSANTS POUVANT PROVOQUER DES ARCS ÉLECTRIQUES OU DES
ÉTINCELLES. POUR PRÉVENIR LES RISQUES D’INCENDIE OU D’EXPLOSION, NE PAS INSTALLER LE PRODUIT
DANS UN COMPARTIMENT CONTENANT DES PILES OU DES MATÉRIAUX INFLAMMABLES. • RISQUE DE
DÉCHARGE ÉLECTRIQUE. UTILISER UNIQUEMENT LE RÉCEPTACLE D’INTERRUPTEUR DE CIRCUIT DE MISE À LA
MASSE OU LE COUPE-CIRCUIT INDIQUÉS DANS LE MANUEL D’INSTALLATION ET D’UTILISATION FOURNI AVEC CE
PRODUIT. LES AUTRES TYPES PEUVENT NE PAS FONCTIONNER CORRECTEMENT LORSQU’ILS SONT
CONNECTÉS À CE PRODUIT. • RISQUE DE DÉCHARGE ÉLECTRIQUE, PUITS THERMIQUES NON MIS À LA TERRE,
TESTER AVANT DE TOUCHER. • PRÉVU POUR UNE UTILISATION CONTINUE.
DANGER:
• TO REDUCE THE RISK OF EXPLOSION - DO NOT INSTALL IN MACHINERY SPACE OR AREA IN WHICH IGNITION
- PROTECTED EQUIPMENT IS REQUIRED.
• POUR RÉDUIRE LE RISQUE D’EXPLOSION, NE PAS INSTALLER LE PRODUIT DANS UN COMPARTIMENT
MACHINE OU UNE ZONE CONTENANT UN ALLUMAGE — L’ÉQUIPEMENT PROTÉGÉ EST EXIGÉ
CB2
INPUT
50A
CB1
INPUT
50A
Temperature Sensor
®
®
MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA
●
DC Input: 12.6V
●
Maximum Continuous Input Current: 267ADC
●
Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
●
Maximum Continuous Output Current: 16.7AAC
●
Surge Power: 3400 Real Watts (5 seconds)
●
THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100 [email protected] VDC nominal with 120 VAC / 60Hz (15 AAC) input
●
Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC
●
Input Voltage: 120 VAC
●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000 VA
●
DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz
●
Generator Input Frequency Range: 50 to 70Hz
●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER
E483757
®
MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA
●
DC Input: 12.6V
●
Maximum Continuous Input Current: 267ADC
●
Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
●
Maximum Continuous Output Current: 16.7AAC
●
Surge Power: 3400 Real Watts (5 seconds)
●
THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100 [email protected] VDC nominal with 120 VAC / 60Hz (15 AAC) input
●
Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC
●
Input Voltage: 120 VAC
●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000 VA
●
DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz
●
Generator Input Frequency Range: 50 to 70Hz
●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER
E483757
®
MODEL: GP-IC2000-12 Inverter / Charger
gpelectric.com
Inverter Operation
●
Continuous Output Power (-20~40°C): 2000VA
●
DC Input: 12.6V
●
Maximum Continuous Input Current: 267ADC
●
Nominal AC Output Voltage/Frequency: 120VAC(±5%)/60Hz(±0.1Hz)
●
Maximum Continuous Output Current: 16.7AAC
●
Surge Power: 3400 Real Watts (5 seconds)
●
THD: <5%
Charger Operation
Bypass Operation
Continuous Charger Current (-20~40°C) : 100 [email protected] VDC nominal with 120 VAC / 60Hz (15 AAC) input
●
Input / Output Voltage: 120 (L1-N) / 120 (L2-N) VAC
●
Input Voltage: 120 VAC
●
●
●
Maximum AC Input Current: 50 AAC
●
Maximum Power: 12000 VA
●
DC Output Range: 8.5 to 16.5VDC
Grid Input Frequency: 60Hz
●
Generator Input Frequency Range: 50 to 70Hz
●
Power Factor: >0.98
Conforms to UL 458 (6th Ed.) and UL STD 1741 (2nd. Ed.)
Certified to CSA C22.2 No. 107.1-01
5GW2
MQ7275
MARINE POWER INVERTER
5DA7
E198012
POWER INVERTER
E483757
4.9"
(12.45cm)
2.8"
(7.1cm)
INSTALLATION