Leak Sensor Advanced User Manual
Compatible Command Classes
Command Class
Notes
Device Reset Locally V1 (0x5A)
-
Powerlevel V1 (0x73)
-
Battery V1(0x80)
-
Association Group Information V1 (0x59)
-
Z-Wave Plus Info V2 (0x5E)
Returned Value:
01 06 00 0C 05 0C 05
Z-Wave Plus Version:
01
Role Type
: 06
(Slave Sleeping Reporting)
Node Type
: 00
(Z-Wave Plus Node)
Installer Icon Type
: 0C 05
(Water Alarm)
User Icon Type
: 0C 05
(Water Alarm)
Version V2 (0x86)
Returned Value:
06 04 05 02 28 10 00
Z-Wave Library Type:
06
(Routing Slave)
Protocol Version
: 04 05
Protocol Sub-Version
: 02 28
Application Version
: 10
Application Sub-Version
: 00
Manufacturer Specific V2 (0x72)
Returned Value:
02 1F 03 01 85
Manufacturer ID:
02 1F
Product Type
: 03
Product ID
: 00 85
Wake Up V2 (0x84)
The wake-up interval is set in seconds, and is 43,200 seconds (12 hours)
by default. The wake-up interval can be set to any value from 300s (5
minutes) to 16,777,200s (about 190 days) in 60-second increments.
Binary Sensor (0x30)
The Leak Sensor also sends a Binary Sensor Report when a leak is
detected or removed. See below for the SENSOR_BINARY_REPORT
parameters sent:
Sensor Type
: 06
(Water)
Leak Detected Value
: 0xFF
Leak Removed Value
: 0x00