X1 SERIES ELEVATOR CONTROLLER INSTALLATION & PROGRAMMING GUIDE | DIGITAL MONITORING PRODUCTS
9
+AC/DC-
+BAT-
R1 W1 G1
B1
LC BC
R2 W2 G2 B2 LC BC
DS RX CI
G
01
02 12V
NC
C
NO
DR
Y WE
T
12 V Battery
-
+
Orange/Brown
(Wiegand LED)
Card
Reader
Red
White
Green
Black
Transformer
-
+
Power Indicator
Custom
Input
G
CI
AUX
Output 1
O1
12V
O2
AUX
Output 2
12V
XX
= wire polarity or terminal location
PWR
DATA
0 1
2
3
4
5
6
7
8
9
ADDR
6
1
7
8
9
10
2
3
4
5
NC 1 NO
NC 2 NO
NC 3 NO
NC 4 NO
NC 5 NO
NC 6 NO
NC 7 NO
NC 8 NO
NC 9 NO NC 10 NO
Elevator
Equipment
Panel
STEP 6: APPLY POWER
Warning:
Refer to your local state regulations before connecting to building power� Wiring methods
shall be in accordance with NEC, NFPA #72, ANSI, and with all Authority Having Jurisdiction
Wire the Input Power
Connect the transformer wires or external power to terminals 1 and 2 on the X1
PCB� Use no more than 70 ft� of 16 gauge or 40 ft� of 18 gauge wire between the
transformer and the X1 PCB�
Wire the Battery
DMP recommends using a 9 Ah battery� Connect the red battery lead to the
battery positive terminal� Connect the black battery lead to the negative battery
terminal� Observe polarity when connecting the battery�
Wiring Example
The diagram here shows the transformer and the battery wiring�
Battery Harness
Red
12 V Battery
-
+
+AC/DC-
+BAT-
+
-