X1 SERIES ELEVATOR CONTROLLER INSTALLATION & PROGRAMMING GUIDE | DIGITAL MONITORING PRODUCTS
15
ADDITIONAL INFORMATION
LEDs
LED
Meaning
PWR/BOOT
On when board is powered and operating
READER 1
Turns on for one second to indicate receipt of a valid input from the In Reader determined by card
format programming
READER 2
Turns on for one second to indicate receipt of a valid input from the Out Reader determined by card
format programming
RELAY
On when elevator relay is active
DATA
Not used on X1
FIRE
This is not typically used for elevator access�
LOCKDOWN
This is not typically used for elevator access�
Cell Module Removal
1� Unscrew the washer on top of the enclosure and remove the
cell module antenna�
2� Unplug the cell module from the cell header�
3� Pinch the tab of the standoff to release the cell module from
the elevator controller�
X1 Elevator Controller Initialization
Warning:
This process clears all Dealer Admin
programming and defaults the elevator
controller back to factory settings�
1� Place a jumper over the L header of the
elevator controller�
2� Within 15 seconds, place a jumper on the
center two pins of the 4-wire connector (short
the green and yellow together)� Reader 1,
Reader 2, Fire, and Lockdown operation LEDs
turn on�
3� Within 15 seconds, remove both jumpers� The
above LEDs will turn off� The Power LED will
turn on steady to indicate the factory default
is complete�
Tab
LC BC
DS RX CI
G
01
02 12V
NC
C
NO
PWR/BOOT
READER 1
READER 2
RELAY
DATA
FIRE
LOCKDOWN
R
L
PWR/BOOT
READER 1
READER 2
RELAY
DATA
FIRE
LOCKDOWN
R
L
L Terminal
4-Wire
Connector
Operation
LEDs