1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0                                

 

31/40

 

 

17.7 

P

ROPORTIONAL 

O

UTPUT 

F

OR 

F

AN 

C

ONDENSING 

C

ONTROL  OR 

FO

C

OMPRESSOR 

I

NVERTER 

C

ONTROLLED OR 

F

OR 

A

UXILIARY 

O

UTPUTS

 

OUT1…OUT

= signals for the modulation of the condenser fan

 

GND

 = ground for pressure transducers 

 

 

Summary of Contents for Emerson iChill IC100CX EVO

Page 1: ...QUICK REFERENCE GUIDE IC100CX EVO rel 1 0 ...

Page 2: ......

Page 3: ...AN ALREADY PROGRAMMED HOT KEY DOWNLOAD 12 9 2 HOW TO COPY THE PARAMETER MAP INTO THE HOT KEY UPLOAD 12 10 PROGRAMMING USING LOCAL USER INTERFACE 13 10 1 ENTER PARAMETERS PROGRAMMING LEVEL PR1 13 10 2 ENTER PARAMETERS PROGRAMMING LEVEL PR2 13 10 3 ENTER PARAMETERS PROGRAMMING LEVEL PR3 14 11 MENU MENU KEY 14 11 1 ALARM LIST READ AND RESET 15 11 2 ALARM LOG LIST 15 12 REMOTE KEYBOARD VI613 16 13 REM...

Page 4: ...ARY OUTPUTS 31 17 8 PROPORTIONAL OUTPUT 0 10V TO CONTROL DUMPER MOTORS 32 17 9 PROPORTIONAL OUTPUTS CONFIGURED FOR AUX RELAY CONTROL 34 17 10 CONNECTION TO THE ELECTRONIC EXPANSION VALVE DRIVER IEV22D OR IEV12D 35 18 INSTALLING AND MOUNTING 36 18 1 PANEL CUT OUT 36 18 2 VERTICAL BOARDS VI613 PANEL CUT OUT 36 19 ELECTRICAL CONNECTIONS 37 20 TECHNICAL DATA 38 20 1 SUPPLY VOLTAGE 38 20 2 ANALOGUE INP...

Page 5: ...ent back to the distributor or to Dixell S r l with a detailed description of the fault Consider the maximum current which can be applied to each relay see Technical Data Ensure that the wires for probes loads and the power supply are separated and far enough from each other without crossing or intertwining do not use the same electrical conduit to install high voltage cabling and low voltage cabl...

Page 6: ...cipal waste but to separate the waste Public or private collection points must be used to dispose of the goods in accordance with local laws Furthermore at the end of the product s life it is also possible to return this to the retailer when a new purchase is made This equipment may contain hazardous substances Improper use or incorrect disposal can have adverse effects on human health and the env...

Page 7: ...OG INPUTS 4 NTC or PTC or Digital input 2 NTC or PTC or 4 20mA or 0 5Volt or Digital input Configurable Configurable PROPORTIONAL OUTPUTS 2 signal 0 10V Configurable Configurable 2 signal 0 10V or PWM only for condenser fan control to connect to XV__PK series Configurable Configurable SERIAL OUTPUTS TTL Mod BusRtu protocol Remote panel VI613 up to 2 remote keyboards or one V2I810 LCD panel or one ...

Page 8: ...ws a temperature or pressure Lighted when the bottom display shows the clock Lighted during the programming parameters if it is time based Lighted in function menu when the display shows the defrost delay Alarm blinking in case of alarm Lighted when sanitary hot water function is active Lighted after pressing menu button Lighted if anti freeze heaters integration heating boiler are activated ...

Page 9: ...running AUX Lighted when auxiliary function is active Lighted when the controller is ON in cooling or heating FC Lighted when the Free cooling is active Lighted when the defrost is activated Blinking when the delay to activate the defrost is active 5 DISPLAY LAYOUT Pressing Up or Down button the display shows the temperature or pressure of the main probes configured in the instrument The lower dis...

Page 10: ...sanitary circuit in case it is enabled If the instrument is in chiller operation lower display shows SetH set heat pump press SET key again lower display shows SEtr set real of operation in the case where the Energy Saving and or function dynamic set point are active press SET key again lower display shows SEtS set sanitary circuit in case it is enabled 6 2 MODIFY THE SET POINT push SET key for at...

Page 11: ...meter to change the value of the parameter Push once To turn ON or turn OFF the controller in chiller or heat pump depending from CF59 parameter Push once To turn ON or turn OFF the controller in chiller or heat pump depending from CF59 parameter Push once To enter the function Menu Push for 3 seconds To set the clock only for controller with clock on board Pushing once during the programming To e...

Page 12: ...onth 0 31 MntH month 1 12 yEAr year 00 99 9 PARAMETERS PROGRAMMING WITH THE HOT KEY 64 9 1 HOW TO PROGRAM THE INSTRUMENT WITH AN ALREADY PROGRAMMED HOT KEY DOWNLOAD 1 Power off the instrument 2 Insert the hot key already programmed by software Wizmate or other instrument 3 Power on the instrument 4 Automatically the parameters are downloaded During the download the regulation is locked and the top...

Page 13: ...verload alarm is 4 Passwords can be customized using specific parameters in the case in which it is necessary to access the parameters and the passwords have been changed it is necessary to contact the machine manufacturer to obtain the necessary information 10 1 ENTER PARAMETERS PROGRAMMING LEVEL PR1 Enter the Pr1 User level 1 Push SET DOWN keys together for 3 seconds The top display shows PAS an...

Page 14: ...how Pr3 4 Push SET key and the top display shows 0 blinking 5 Push UP or DOWN to select Pr3 password 6 Push SET and if the value is correct the top display shows the first family of parameters ALL 7 Push UP or DOWN to select the parameter family 8 Push SET to enter the bottom display shows the first available parameter label while the top display shows its value 9 Push UP or DOWN to modify its val...

Page 15: ... key Nothing happens if there are not alarms 4 The bottom display shows the alarm code and the top display shows the label rSt if it is possible to reset the alarm or NO if it is not possible to reset the alarm 5 Push UP or DOWN to scroll the alarm list if more than one alarm is active 6 Repeat the reset procedure for each alarm 7 To exit the ALrM reset push MENU or wait the timeout 11 2 ALARM LOG...

Page 16: ...0 9 To exit push the MENU key or wait the timeout The standard password to reset the alarm log is 4 12 REMOTE KEYBOARD VI613 The display visualization and the button functions are the same of the Ichill then refer to previous chapters of the quick reference guide ...

Page 17: ...CX EVO rel 1 0 17 40 13 REMOTE LCD PANEL VGI810 OR V2I810 Two models of remote LCD panel are available VGI810 Visograph 1st series V2I810 Visograph IInd seres The description of the user interface is available in the user manual of the Visograph ...

Page 18: ...r air unit Evaporator Pump Supply fan Condenser Pump Domestic hot water Water pump Solar panel Water pump Condenser fan Auxiliary relay ACF1 AC16 Configuration alarm OFF OFF OFF OFF OFF OFF OFF OFF OFF ACFL Condenser flow alarm OFF 4 8 8 8 OFF 3 8 8 8 8 AEE Eeprom alarm OFF OFF OFF OFF OFF OFF OFF OFF OFF AEFL Evaporator flow alarm OFF 4 OFF boiler 8 OFF 3 8 8 8 8 8 AEht High inlet evaporator wate...

Page 19: ...r2 Remote keyboard probe alarm OFF 3 OFF 3 OFF 3 OFF 3 OFF 3 OFF 3 OFF 3 OFF 3 OFF 3 APU1 APU4 IEV Electronic Expansion Valve probe alarm 7 7 7 7 7 7 7 7 ASLA Serial communication failure with I O expansion OFF OFF OFF OFF OFF OFF OFF OFF AtAS Domestic hot water pump overload OFF 6 8 8 8 8 8 8 AtC1 Condenser 1 water pump overload alarm OFF 4 8 8 8 OFF 8 8 OFF 8 AtC2 Condenser 2 water pump overload...

Page 20: ...re OFF only if the probe of the remote keyboard is set as regulation probe 4 The compressors are Off if the water pump is the only configured water pump if 2 water pumps are configured the compressors are OFF if both water pumps are in alarm or not available 5 Boiler heaters off if the water pump is the only configured water pump if 2 water pumps are configured the compressors are OFF if both wate...

Page 21: ... transducer or by high pressure transducer if only one pressure transducer is configured OFF OFF b1lP Low condenser temperature OFF OFF b1PH Pump down alarm during the switching off the compressor OFF OFF b1PL Pump down during the switching on the compressor OFF OFF b1tF Fan overload OFF OFF b1UA Expansion valve 1 or valve 2 alarm OFF OFF 15 3 COMPRESSOR ALARM Alarm Code Alarm description Compress...

Page 22: ...ays loses the time and the date ArtF Clock failure C n Mn Compressor n maintenance b1Cu Unloading by high or low evaporator or condenser temperature or pressure b1Cu Unloading by low evaporator temperature or pressure b1rC Recovery function disabled b1Eu Unloading by low evaporator outlet temperature noL Link problem between the Ichill and the remote keyboard 16 BLACK OUT After the black out when ...

Page 23: ...PTC 2 temperature probes NTC PTC pressure transducer 4 20 mA pressure transducer ratio metric 0 5 0 Volt 4 modulating outputs 2 0 10 Volt 2 0 10 0 Volt or PWM for modulating condenser fan 1 output to connect the remote panel max 2 VI613 remote keyboards or 1 Visograph or 1 Visotouch 1 LAN to connect an IEV electronic expansion valve driver 1 TTL output to connect Hot key 64 for parameters programm...

Page 24: ...erature probes NTC PTC pressure transducer 4 20 mA pressure transducer ratio metric 0 5 0 Volt 4 modulating outputs 2 0 10 Volt 2 0 10 0 Volt or PWM for modulating condenser fan 1 output to connect a remote panel max 2 VI613 remote keyboards or 1 Visograph or 1 Visotouch 1 LAN to connect an IEV electronic expansion valve driver 1 TTL output to connect Hot key 64 for parameters programming XJ485CX ...

Page 25: ...mote terminal VI613 is provided with probe on board the temperature adjustment can be performed with the probe of the terminal The connection of the remote terminals must be performed using a shielded twisted cable such as Belden 8772 wires 1 mm2 minimum the maximum length of VI613 terminal cable is 100 mt maximum length of the connection both if using one or two keyboards the maximum length of V2...

Page 26: ...1592022010 Quick reference guide iCHILL 100CX EVO rel 1 0 26 40 VI613 LED panel VGI810 or V2I810 LCD PANEL ...

Page 27: ...1592022010 Quick reference guide iCHILL 100CX EVO rel 1 0 27 40 VTIC10 TOUCH PANEL 17 2 ANALOG INPUTS NTC PTC PROBES PbC common terminal Pb1 Pb6 probe inputs ...

Page 28: ...1592022010 Quick reference guide iCHILL 100CX EVO rel 1 0 28 40 17 3 DIGITAL INPUTS GND common terminal ID1 ID11 digital inputs ...

Page 29: ...RANSDUCER PP30 4 20MA SIGNAL 12V power supply for pressure transducers Pb3 and Pb4 pressure transducer inputs 17 5 ANALOG INPUT FOR PRESSURE RATIOMETRIC TRANSDUCER PPR30 0 5V SIGNAL 5V power supply for pressure transducers GND ground for pressure transducers Pb3 and Pb4 pressure transducer inputs ...

Page 30: ...M OUTPUT FOR CONDENSING FAN SPEED CONTROL OUT3 and OUT4 signals for the modulation of the condenser fan GND ground for pressure transducers The compatible modules are the following XV05PK mono phase 500 Watt 2A XV10PK mono phase 1000 Watt 4A XV22PK mono phase 2200 Watt 9A ...

Page 31: ...HILL 100CX EVO rel 1 0 31 40 17 7 PROPORTIONAL OUTPUT FOR FAN CONDENSING CONTROL OR FOR COMPRESSOR INVERTER CONTROLLED OR FOR AUXILIARY OUTPUTS OUT1 OUT4 signals for the modulation of the condenser fan GND ground for pressure transducers ...

Page 32: ...PER MOTORS OUT1 OUT4 signals for the modulation of the dumper motor GND ground If the dumper motor has a common line between a pole of the power supply and the pole of the 0 10V signal it is necessary to use two transformers for the power supply of the controller Ichill and the power supply of the dumper motor ...

Page 33: ...1592022010 Quick reference guide iCHILL 100CX EVO rel 1 0 33 40 ...

Page 34: ...1592022010 Quick reference guide iCHILL 100CX EVO rel 1 0 34 40 17 9 PROPORTIONAL OUTPUTS CONFIGURED FOR AUX RELAY CONTROL OUT1 OUT4 signals for relays GND ground ...

Page 35: ...uide iCHILL 100CX EVO rel 1 0 35 40 17 10 CONNECTION TO THE ELECTRONIC EXPANSION VALVE DRIVER IEV22D OR IEV12D The Ichill 100CX EVO can be connected to an Eletctronic expansion valve driver IEV22D or IEV12D through LAN connection ...

Page 36: ... out 71x29mm and fixed using the special supplied bracket Avoid locations subject to heavy vibration corrosive gases or excessive dirt Ensure ventilation around the instrument 18 2 VERTICAL BOARDS VI613 PANEL CUT OUT The keyboard must be mounted on vertical panel with cut out 72x56 mm and screwed with two screws The IP65 can be reached with the gasket RGW V optional ...

Page 37: ...ays for power supplay digital and analogue inputs and modulating outputs 1 removable terminal blocks AMP 12 ways for the relay outputs 5 ways connector for TTL RS485 interface outputs Wire size signal cable AWG 24 power supply cable AWG 22 relay output AWG 17 General notes Keep low voltage cables such as analogue digital inputs outputs and probes away from power cables Respect the minimum load cur...

Page 38: ...NTC PTC Digital input 2 NTC PTC 4 20mA 0 5V Digital input Type of analogue input configurable via software parameter NTC 50T110 C 10KΩ 1 a 25 C PTC 50T150 C 990Ω 1 a 25 C Rathiometric 0 5 4 5V Current 4 20mA Digital input free contact Operation range 50 C 110 C 58 F 230 F NTC probe 50 C 150 C 58 F 302 F PTC probe 0 bar 50 bar 0 psi 302 psi pressure probe Resolution 0 1 C 1 F 0 1 bar 1 psi 20 3 DIG...

Page 39: ...UTS Type Relays with NO contacts Number of outputs 6 IC106CX model 8 IC108CX model Maximum load 5A 250Vac SPST 5 2 A Note Verify maximum current of the loads and maximum current of the common line of the relay 10A max There is double insulation between the digital outputs and the low voltage of the rest of the circuit Do not use different voltages for the two groups of relays Some contactors can p...

Page 40: ...ensions Frontal panel 32x74mm depht 60mm Mounting Panel mounting in a 29x71mm panel cut out Material Thermoplastic PC ABS Selfhestinguish V0 UL94 IP protection IP65 20 7 OPERATING AND STORAGE TEMPERATURE Operating temperature 10 C 55 C Storege temperature 30 C 85 C Operating humidity 20 85 not condensing ...

Reviews: