1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
37/40
WALL MOUNTING: use the vertical V-KIT (black, white and grey) as described in the following scheme:
19
ELECTRICAL CONNECTIONS
The instrument is provided with:
•
2 removable terminal blocks MOLEX MICROFIT 14 and 18 ways for power supplay / digital and analogue
inputs and modulating outputs
•
1 removable terminal blocks AMP 12 ways for the relay outputs
•
5 ways connector for TTL RS485 interface outputs.
Wire size:
•
signal cable AWG 24
•
power supply cable AWG 22
•
relay output AWG 17
General notes:
•
Keep low voltage cables, such as analogue/digital inputs/outputs and probes, away from power cables.
•
Respect the minimum load current of each relay output, in case of power loads use filtered contactors.