1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
39/40
20.4 A
NALOGUE OUTPUTS
Type:
Non opto-insulated, internal power
Number of outputs:
4
Type of analogue output:
(configurable via software
parameter)
4 configurable outputs:
- OUT1/OUT2: 0-10Vdc
- OUT3 and OUT 3:
•
0-10Vdc
•
PWM (to use with Dixell XV series fan controllers)
Maximum load:
40mA
Accuracy:
±2% full scale
Note:
The electrical devices controlled by these analogue outputs
must be powered separately with another transformer (do not
use the same secondary of the controller's power) in order to
prevent the outputs from malfunctioning or being damaged.
20.5 D
IGITAL OUTPUTS
Type:
Relays with NO contacts
Number of outputs:
6: IC106CX model
8: IC108CX model
Maximum load:
5A(250Vac) SPST 5(2)A
Note:
Verify maximum current of the loads and maximum current of
the common line of the relay (10A max).
There is double insulation between the digital outputs and the
low voltage of the rest of the circuit.
Do not use different voltages for the two groups of relays.
Some contactors can produce very high electrical stresses on
the
relay
contacts
mounted
in
the
device.
Dixell suggests to carefully check the technical documentation
of the contactors and follow the instructions contained in this
doumentation (commercial documentation is not a reference
for theese information). To protect the relay contacts of the
device, verify the need to use electrical disturbance
suppressors or excess voltage protections