1592022010 Quick reference guide iCHILL 100CX EVO rel. 1.0
24/40
17.2
IC108CX:
H
ARDWARE
R
ESOURCES
•
8 digital outputs (relays):
max current on the relay contacts relè 5(2)A 250V
max current on the common line 10A 250V
•
11 digital inputs:
(free of voltage)
•
analogue inputs:
•
4 temperature probes (NTC / PTC)
•
2 temperature probes (NTC / PTC) / pressure transducer 4÷20 mA / pressure transducer ratio-
metric 0÷ 5.0 Volt
•
4 modulating outputs:
•
2 (0 ÷ 10 Volt)
•
2 (0 ÷ 10.0 Volt or PWM*) (*for modulating condenser fan)
•
1 output to connect a remote panel (max 2 VI613 remote keyboards or 1 Visograph or 1 Visotouch)
•
1 LAN to connect an IEV electronic expansion valve driver
•
1 TTL output to connect:
•
Hot key 64 for parameters programming
•
XJ485CX (interface to convert TTL signal to RS485 signal) for monitoring systems (XWEB or
third-party system)