19
19
ESIM022 User manual v1.1
Set input mode
as Temperature
Sensor
SMS
SMS text message content:
ZONE2:TEMP
Example:
Z2:TEMP
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
Set input mode as
Digital
SMS
SMS text message content:
ZONE2:DIG
Example:
Z2:DIG
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
View input mode
parameters
Config
Tool
This operation may be carried out from the PC using the
ELDES Configuration Tool
software.
8.2.1 Digital Mode
When Digital mode is set, the system follows this pattern:
a) Monitors input voltage ranging from 0 mV through 3000 mV every 100 millisecond.
b) Verifies if the set up threshold (by default – 1500 mV) is not exceeded.
c) By default, the input is set as NO (normally open), therefore if the voltage drops below
the threshold, it will result in input state change to alarm followed by notifying the user
by SMS text message and/or phone call.
d) When the voltage rises above the threshold, it will result in input state change to restore
followed by notifying the user by SMS text message and/or phone call (only for alarm
state).