CLM–36
©
Dinel, s.r.o.
17
Optional (see datasheets "Accessories")
•
Connector with protection class IP67
(GAN–DADE 7A) with 5 m cable (current
output)
•
Connector with protection class IP67
(GAN–DAAE 7A) with 5 m cable (voltage
output)
•
Steel welding flange
ON–36x2
•
St. steel welding flange NN–36x2
Level meter CLM–36 is equipped with protection against electric shock on electrode, reverse polarity,
output current overload, short circuit and short time over voltages.
Protection against dangerous contact is secured by low safety voltage that complies with
EN 33 2000-4-41.
Electromagnetic compatibility is provided by conformity with standards: EN 55022/B, EN 61326-1,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6.
Explosion proof of CLM–36Xi is examined by FTZÚ-AO 210 Ostrava - Radvanice certificate No.:
FTZÚ 02 ATEX 0235X.
Special conditions for safe use of variant CLM–70Xi
Equipment is designed to be connected to isolating repeater IRU-420
If other approved apparatus is used, which output parameters comply with above mentioned input
parameters it is necessary to have an galvanic separation or in a case of apparatus without galvanic
separation (Zener barriers) it is necessary to provide equipotential equalizing between sensor and
barrier earthing point.
Design CLM-36Xi can be used in zone 0 or zone 20. With design CLM-36XiT can be only used in
zone 0 and zone 20 electrode part and head with electronics can be used only in zone 1 or zone 21.
Maximum temperature of electrodes is equal to temperature of measured medium.
When used in zone 0 the present explosive atmosphere of air mixture and gases, vapours or mists
must comply with: - 20°C < T
amb
< 60°C 0,8 bar < p < 1,1 bar
15 . s
afety
,
protections
,
coMpatibility
and
explosion
proof
•
St. steel fixing nut UM–36x2
•
Anchor welding cylinder KV–31
(only CLM–36–31)
•
Dust-tight bushing PR–31
(only CLM–36–31)