CLM–36
©
Dinel, s.r.o.
9
VARIANTS WITH REFERENCE TUBE
CLM-36_-20, 22
h
-
the distance from the bottom
- min. 50 mm with respect on
possibility of presence of heavy
fraction (water) in oil products
k
-
the distance from the wall -
optional
DEEP VESSELS, CONTAINERS AND SILOS
CLM-36_-30, 32
connection to the armouring
E – The length of electrode - the lower end of the electrode has to be
dipped - min. 20 mm below the lowest measured level
h – The distance from the bottom - min. 100 mm
a – The distance from the wall - at least E/20, as far as possible
from the walls, to the middle between the wall and the vertical inlet
concrete silo
metal tank
Fig. 5: Installation of level meter with reference tube
Fig. 6: Installation of level meter with rope electrode