EN-14
452237.66.53 · FD 9912
www.gdts.one
English
WI 120TU - WI 180TU
9
Heat output / COP
9.1
Heat output / coefficient of performance (COP)
6
EN 14511
Performance level
1
2
at W10 / W55
kW / ---
52.1 / 3.7
104.2 / 3.7
at W10 / W45
kW / ---
55.9 / 4.7
109.5 / 4.6
at W10 / W35
kW / ---
61.6 / 6.1
118.5 / 5.9
1. The specified sound pressure level corresponds to the operating noise of the heat pump in heating operation at 55 °C flow temperature.
The specified sound pressure level represents the free sound area level. The measured value can deviate by up to 16 dB(A), depending on the installation location.
2. Note that additional space is required for pipe connections, operation and maintenance.
3. These data indicate the size and capacity of the system according to EN 14511. For an analysis of the economic and energy efficiency of the system, the bivalence point and
regulation should be taken into consideration. These specifications can only be achieved with clean heat exchangers. Information on maintenance, commissioning and oper-
ation can be found in the respective sections of the installation and operating instructions. The specified values, e.g. W10 / W55, have the following meaning: Heat source
temperature 10 °C and heating water flow temperature 55 °C.
4. See CE declaration of conformity
5. The heat circulating pump and the heat pump manager must always be ready for operation.
6. The coefficients of performance are valid with the circulating pumps included in the scope of supply.
1
Type and order code
WI 180TU
2
Design
Heat source
Water
2.1
Model
Universal
2.2
Controller
integrated
2.3
Thermal energy meter
Integrated
2.4
Installation location
Indoors
2.5
Performance levels
2
3
Operating limits
3.1
Heating water flow
°C
20 to 62 ± 2
3.2
Cold waterRC (heat source)
°C
+7 to +25
4
Flow / sound
4.1
Heating water flow / free compression (max).
Nominal flow in accordance
at W10...7 / W35...28
m³/h / Pa
22.2 / 40000
at W10...7 / W45...38
m³/h / Pa
21.2 / 43500
at W10...7 / W55...45
m³/h / Pa
14.4 / 64000
Minimum heating water flow
m³/h / Pa
14.4 / 64000
4.2
Cold water flow rate / internal pressure differential
Nominal flow in accordance
at W10...7 / W35...28
m³/h / Pa
42.1 / 41500
at W10...7 / W45...38
m³/h / Pa
37.2 / 32500
at W10...7 / W55...45
m³/h / Pa
34.7 / 28000
Minimum cold water flow rate
m³/h / Pa
34.7 / 28000
4.3
Sound power level according to EN 12102
dB(A)
70
4.4
Sound pressure level at a distance of 1m
1
dB(A)
55
5
Dimensions, weight and filling quantity
5.1
Device dimensions
2
H x W x L mm
1890 x 1350 x 750
5.2
Weight of the transportable unit(s) incl. packaging
kg
824
5.3
Device connections for heating
inches
Rp 2½“
5.4
Device connections for heat source
Inches
Rp 3“
5.5
Refrigerant / total filling weight
type/kg
R410A / 19.5
5.6
GWP value / CO
2
equivalent
--- / t
2088 / 41
5.7
Refrigeration circuit hermetically sealed
yes
5.8
Lubricant / total filling quantity
type/litres
Polyolester (POE) / 14.6
5.9
Volume of heating water in device
Litres
26
5.10 Volume of heat transfer medium in device
Litres
26
6
Electrical connection
6.1
Supply voltage / fuse protection / RCD-Type
3~/PE 400 V (50 Hz) / C 100A / A
6.2
Control voltage / fuse protection / RCD-Type
1~/N/PE 230 V (50 Hz) / C 13A / A
6.3
Degree of protection according to EN 60 529
IP 21
6.4
Starting current with soft starter
A
110
6.5
Nominal power consumption W10 W35 / max. power consumption
3
kW
32.1 / 57.5
6.6
Nominal current W10 W35 / cos
A / ---
57.9 / 0.8
Summary of Contents for WI 120TU
Page 2: ......
Page 38: ...EN 18 452237 66 53 FD 9912 www gdts one English WI 120TU WI 180TU...
Page 56: ...FR 18 452237 66 53 FD 9912 www gdts one Fran ais WI 120TU WI 180TU...
Page 82: ...A XXVI 452237 66 53 FD 9912 www gdts one Anhang Appendix Annexes WI 120TU WI 180TU...
Page 83: ...www gdts one 452237 66 53 FD 9912 A XXVII WI 120TU WI 180TU Anhang Appendix Annexes...