LWP 200E
English
7.2 Menu structure
Parameter change: The menu is accessed using the
key. In
this menu, changes can be made to parameters. The desired
menu item is selected using the
and
keys, which are
marked with the cursor symbol
. The submenu is accessed
using the
key.
In this submenu, the parameter that is to be changed can be se-
lected (also using the arrow keys). The value to be changed is
displayed in "bold" using the
key, and can then be changed
using the arrow keys. The entry is completed by pressing the
key again.
M
OK
OK
OK
Display
Description
Setting range
Settings
Time
Sets the current time
00:00
Weekday
Sets the current weekday
Mo
….
Su
Language
Sets the desired language
EN
EN
FR
Domestic hot water
Nominal value
Sets the desired domestic hot water setpoint
25
...45 °C...
60
Hysteresis
Sets the switching hysteresis
2
..0.3K...
10
Min. temperature
Sets the minimum hot water temperature, which should also not be undershot for the
duration of a programmed shut-off time.
15
...25 °C...
40
Time programs
HP block
Time
Sets the start and end time for a heat pump block
00:00 -
00:00
Day
Sets the weekday / block of days on which the heat pump block should be activated
Mo - Su (day)
Mo - Fr (block)
Sa - Su (block)
Mo - Su (block)
Thermal disinfection
Time
Sets the start time for thermal disinfection
00:00:00
Nominal value
Sets the set temperature for thermal disinfection. The flange heater is also used addition-
ally for this function
60
...65 °C...
(65 °C)
Day
Sets the day on which thermal disinfection should be activated
Mo - Su (day)
Mo - Fr (block)
Sa - Su (block)
Mo - Su (block)
Ventilation
Ventilation
Activates the ventilation function. Continuous operation of the fan is also possible inde-
pendent of domestic hot water preparation in order to ensure air circulation or an exhaust
air function. The speed and thus the volume flow can be set as a percentage. 100% cor-
responds to a volume flow of 450 m³/h. 0% means that the fan is switched off outside of
domestic hot water preparation.
20%
….
100%