EN-34 459462.66.01 · 10/14/B
www.dimplex.de/en
E
n
g
lis
h
FSR 15-35 / FSR 15-35 GS / FSR 15-35 GW
5.4 Electrical connection
ATTENTION!
Comply with the relevant VDE, EN and IEC standards
when connecting the storage heater's electrical
connections. Ensure compliance with the technical
connection requirements of the energy/power supplier!
Fig. 27: Insert the electrical cables and make sure they are
not subject to strain (A). Reduce the length of the cables so
that they cannot come into contact with the heater's hot sur-
faces when it is operating. Do not allow the cables to lie in
loops behind or underneath the storage heater!
The following types of connection are possible:
Fig. 28: Triple-phase supply connection
ATTENTION!
In the case of a fixed connection, the storage heater must
have a isolating device that works across all channels
(phase, neutral, earth), with at least 3 mm contact
distance, installed between it and the mains. This
requirement can be fulfilled by automatic circuit
breakers.
Fig. 29: Mono-phase supply connection
For the mono-phase supply connection, the two copper
bridges from the accessories pack must be fitted between ter-
minals L1 and L2 and between L2 and L3.
Connect phase conductor to terminal L2!
A