DL9120 / DL9130
Operating Instructions
- 29 -
TEST
When the required settings have been selected, press the TEST key to
begin the sequence. The test sequence will perform the following tests at
set test current.
6mA DD Setting
30mA Setting
Display
+6mA
RDC-DD
30mA
Type B
Trip Time
-6mA
RDC-DD
30mA
Type B
Trip Time
30mA 1/2I
Δ
n
0
o
AC
30mA 1/2I
Δ
n
0
o
AC
Trip Time
30mA 1/2I
Δ
n
180
o
AC
30mA 1/2I
Δ
n
180
o
AC
Trip Time
30mA I
Δ
n
0
o
AC
30mA I
Δ
n
0
o
AC
Trip Time
30mA I
Δ
n
180
o
AC
30mA I
Δ
n
180
o
AC
Trip Time
30mA 5I
Δ
n
0
o
AC
30mA 5I
Δ
n
0
o
AC
Trip Time
30mA 5I
Δ
n
180
o
AC
30mA 5I
Δ
n
180
o
AC
Trip Time
The Trip Times are shown in the primary display.
Once the test sequence is complete the results from the sequence can
be reviewed using F3 (Recall) or the sequence can be extended by
pressing TEST to include;
6mA DD Setting
30mA Setting
Display
+6mA
RDC-DD
30mA
Type B
Trip Current
-6mA
RDC-DD
30mA
Type B
Trip Current
30mA
0
o
AC
30mA
0
o
AC
Trip Current
30mA
180
o
AC
30mA
180
o
AC
Trip Current
During the sequence if any test passes and does not trip the RCD then
the DL9130EV will move on to the following test.
If any test passes and does trip the RCD then the DL9130EV will move
onto the following test as soon as the RCD has been reset.
If any test fails then the sequence is aborted.
Once the Trip Current (Ramp) tests have been performed, all of the
results from the test sequence can be reviewed using F3 (Recall).
The following icons will indicate the status throughout the test sequence.
Indicates that the DL9130EV is in EV Mode
Indicates to the user to select the appropriate
Control Pilot (CP) State on the EV adapter.