DL9120 / DL9130
Operating Instructions
- 23 -
The 2 wire mode is disabled for Three Phase Line
Impedance tests.
Rotate the rotary switch until Ze/Zs High is selected. Functions keys F1-
F4 have are used to select the options below:
F1
F2
F3
F4
L-PE loop/
L-N loop
select
Z Max
Not used
Z Auto Start
Note: When the Ze/Zs High switch position is selected, the
DL9130EV will default to the last used setting, even if it has
been switched off.
Auto Start (F4)
When Auto start is activated the Z Auto icon is shown on the display. Loop
measurements will automatically start approximately 3s after the DL9120
/ DL9130EV is connected to correct mains supply via a mains plug or the
test probes. The Auto Start function remains enabled if the switch position
is changed or the DL9120 / DL9130EV is powered off. To disable the Z
Auto Start function press F4.
Note: If the mains supply is removed within the Auto start
countdown period the test will not start.
TEST
To begin the test, press and release the TEST key or select Auto Start
using F4.
When the test is complete, the measurement is shown in the primary
display and the calculated Prospective Short-circuit Current (PSC) is
shown in the secondary display.
5.8 Non trip Earth Loop Impedance / Line Impedance
The DL9120 / DL9130EV will only allow the Earth Loop
Impedance test to be performed if the correct voltages are
detected between line-earth (L-PE illuminated), line-neutral
(L-N illuminated) and neutral-earth (N-PE
not
illuminated).
The DL9120 / DL9130EV can only perform Non trip Earth
Loop Impedance tests if the neutral resistance is <10R.
Should the neutral resistance be above 10R then the
DL9120 / DL9130EV will display the
Hi-N
error.