TROUBLESHOOTING
Problem
Cause
Solution
The maintenance wrench icon appears
in the power meter display.
There is a problem with the inputs
to the power meter.
See the Alert sub-menu or the Diagnostic Alert Modbus Register 146
The display is blank after applying
control power to the meter.
The meter is not receiving
adequate power.
Verify that the meter control power are receiving the required voltage.
Verify that the heart icon is blinking.
Check the fuse.
The data displayed is inaccurate.
Incorrect setup values
Verify the values entered for power meter setup parameters (CT and PT ratings, system
type, etc.). See the Setup section.
Incorrect voltage inputs
Check power meter voltage input terminals to verify adequate voltage.
Power meter is wired improperly.
Check all CTs and PTs to verify correct connection to the same service, CT and PT polarity,
and adequate powering. See the Wiring Diagrams section for more information.
Cannot communicate with power
meter from a remote personal
computer.
Power meter address is incorrect.
Verify that the meter is correctly addressed (see Setup section).
Power meter baud rate is incorrect. Verify that the baud rate of the meter matches that of all other devices on its
communications link (see Setup section).
Communications lines are
improperly connected.
Verify the power meter communications connections (see the Communications section).
Verify the terminating resistors are properly installed on both ends of a chain of units.
Units in the middle of a chain should not have a terminator.
Verify the shield ground is connected between all units.
Sign of one phase (real power) is
incorrect
CT orientation reversed
Remove CT, reverse orientation, reconnect (qualified personnel only)