Motion Sensor - MOSZB-130 – Technical manual
Develco Products A/S
Olof Palmes Allé 40
http://develcoproducts.com
DK-8200 Aarhus N
21
4.4
Temperature Sensor Device – EP 0x26
4.4.1
Temperature Measurement – Cluster id 0x0402
The temperature measurement cluster is described in ZigBee Cluster Library Specification section 4.4
4.4.1.1
Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000
MeasuredValue
Sint16
MinValue to
MaxValue
M
ZCL Reporting is support
DP default is configured
0x0001
MinMeasuredValue
Sint16
0
M
0x0002
MaxMeasuredValue
Sint16
5000
M
4.4.1.1.1
MeasuredValue
The attribute is configured with the following default “ZCL configure reporting” setting.
Min Reporting Interval: 0x003C [60 sec]
Max Reporting Interval: 0x0258 [600 sec]
Reportable Change: 0x000A [0.1 °C]
If the temperature value is stable it will be send every 10 minutes.
If the temperature changes more than 0.1 °C it will be reported but not faster than every 1 minute since last
reporting value.
Note: Min reporting interval 0 sec is invalid when reportable change is configured.
4.4.1.1.2
MinMeasuredValue
The temperature sensor is NOT supporting temperature measurements below 0 degrees Celsius.