Motion Sensor - MOSZB-130 – Technical manual
Develco Products A/S
Olof Palmes Allé 40
http://develcoproducts.com
DK-8200 Aarhus N
17
4.2.5
Time – Cluster id 0x000A
The Time cluster is a general cluster for time it is based on a UTC time in seconds since 0 hrs 0 mins 0 sec on 1st
January 2000. Refer to
[Z2]
for ZigBee specification of the time cluster.
The device will use this clusters as a client – provided that a suitable Time Server is available on the network
(most likely on the Gateway)
4.2.5.1
Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x0000
Time
UTCTime
(Uint32)
Type
range
M
The module will periodically
update its clock by
synchronizing through this
cluster
0x0001
TimeStatus
8 bit bitmap
00000xxx
M
4.2.6
Binary Input Cluster - Cluster id 0x000F
The Binary input cluster is described in ZigBee Cluster Library Specification
4.2.6.1
Attribute
Id#
Name
Type
Range
Man/Opt
Relevance and ref.
0x001C
Description
String
Motion
O
0x0051
OutOfService
Bool
False (0) or
True (1)
M
If True, PresentValue will no
longer follow the physical
input, but will be writeable
0x0055
PresentValue
Bool
False (0) or
True (1)
M
Reflects the state of the
Motion sensor, unless it is
disabled by setting the
OutOfService attribute to
True.
Reportable. Default Min 1
sec, max 10 min
0x0067
Reliabillity
Enum8
O
8 – Process Error: Failure in
the detection circuit
7 – Unreliable Other: Battery
failure, sensitivity reduced.
0 – No Fault Detected
Reportable.