The ArmThreshold_MinTemperature attribute can be used in winter season where the air condition shall warm up 
the room. The MinTemperature attribute is configured to 20 degrees and when movements are detected in the 
room and the temperature is below MinTemperature the air condition is turned on heating the room. 
 

20 degrees

MinTemperature

25 degrees

MaxTemperature

Air Condition

OFF

Air Condition

ON

Cooling

Air Condition

ON

Heating

Temperature

 

4.3.3

 

Occupancy Sensor using illumination sensor input  

End point  0x22,  0x28  and  0x29  can  be  configured  as  a  logic  module  that  controls  the  occupancy  sensor signal 
base on the user defined settings for the illumination sensor input. 
 

Logic module

If Illumination is

 X < TargetLevel

Illuminance measure value

Cluster ID 0x0400

Attribute ID 0x0000

Occupancy state

Occupancy state

 

 
Use case – Energy savings in an office building 

The device is installed to obtain energy savings in an office controlling the light. A ZigBee relay is installed to turn 
on the  light when the occupancy sensor detects movements  in the room. This functionality can be obtained by 
using the standard occupancy sensor Standard functionality - ZCL attributes. 
 
Using the manufacture specific attributes in section 4.2.1.2 provide the user with an extra check before the air light 

is turned on.  
 
The installer can configure the 

TargetLevel 

attribute to a user defined Lux level. When movements are detected in 

the room and the Lux level is below the 

TargetLevel 

the relay turns on the light. 

 

Summary of Contents for MOSZB-130

Page 1: ...Motion Sensor MOSZB 130 Technical manual Revised 05 02 2018 ...

Page 2: ...bject ZDO 8 3 2 IAS Zone 8 3 3 Occupancy Sensor 8 3 4 Temperature Sensor 8 3 5 Light Sensor 8 3 6 Develco Products Utility 8 4 Supported Clusters 10 4 1 Common clusters for each end point 10 4 1 1 Basic Cluster id 0x0000 10 4 1 1 1 Attribute 10 4 1 2 Identify Cluster id 0x0003 10 4 1 2 1 Attribute 10 4 1 2 2 Commands 11 4 2 IAS Zone Device EP 0x23 11 4 2 1 IAS Zone Cluster id 0x0500 11 4 2 1 1 Att...

Page 3: ...or Device EP 0x22 EP 0x28 and 0x29 18 4 3 1 Occupancy sensing Cluster id 0x0406 18 4 3 1 1 Attribute 18 4 3 1 2 Manufacture Specific Attribute 19 4 3 2 Occupancy Sensor using temperature sensor input 19 4 3 3 Occupancy Sensor using illumination sensor input 20 4 4 Temperature Sensor Device EP 0x26 21 4 4 1 Temperature Measurement Cluster id 0x0402 21 4 4 1 1 Attribute 21 4 5 Light Sensor Device EP...

Page 4: ...cal manual Develco Products A S Olof Palmes Allé 40 http develcoproducts com DK 8200 Aarhus N info develcoproducts com 4 6 2 Normal Keep alive 25 6 2 1 Network lost 25 6 3 Low battery 26 7 Specifications 27 8 Contact Information 28 ...

Page 5: ... Develco Products assumes no responsibility for any errors which may appear in this manual Furthermore Develco Products reserves the right to alter the hardware software and or specifications detailed herein at any time without notice and Develco Products does not make any commitment to update the information contained herein All the trademarks listed herein are owned by their respective owners Ro...

Page 6: ...1 Cautionary notes Develco Products A S reserves the right to make changes to any product to improve reliability without further notice Develco Products A S does not assume any liability arising out of the application or use of any product or circuit described herein neither does it convey any license under patent rights or the rights of third parties ...

Page 7: ...figured as Home Automation profile IAS Zone The IAS Zone End point is less sensitive than the Occupancy sensor endpoint Therefore if the device is used as an alarm sensor the IAS Zone end point shall be used 2 1 2 Occupancy The occupancy sensor is PIR based sensing moving objects up to 6 meters from the sensor The off time is adjustable remotely via ZigBee The end point is configured as Home Autom...

Page 8: ...pplication profile Id 0x0104 Home Automation Application device Id 0x0107 Each end point contains a logic module that can be configured to control the occupancy sensor signal base on the user defined settings for the temperature sensor input or the user defined settings for the light sensor input 3 4 Temperature Sensor End point number 0x26 Application profile Id 0x0104 Home Automation Application...

Page 9: ...velcoproducts com 9 Reference documents 053474r18ZB_CSG ZigBee Specification pdf 075123r03ZB_AFG ZigBee_Cluster_Library_Specification pdf 053520r27ZB_HA_PTG Home Automation Profile pdf 075356r15ZB_ZSE ZSE AMI_Profile_Specification pdf They can all be downloaded from http www zigbee org Products DownloadZigBeeTechnicalDocuments aspx ...

Page 10: ... Product s device are all in set 0x000 4 1 1 1 Attribute Id Name Type Range Man Opt Relevance and ref 0x0 ZCLVersion Uint8 Type range M 0x4 ManufacturerName String 0 32 byte O 4 1 1 1 1 0x5 ModelIdentifier String 0 32 byte O 4 1 1 1 2 0x6 DateCode String 0 32 byte O 0x7 PowerSource 8 bit enum Type range M 4 1 1 1 1 Manufacturer name Develco Products A S 4 1 1 1 2 Model identifier MOSZB 130 4 1 1 1...

Page 11: ... cluster is described in ZigBee Cluster Library Specification 4 2 1 1 Attribute Id Name Type Man Opt Relevance and ref 0x0000 Zone State 8 bit Enumeration M 0x0001 Zone Type 16 bit Enumeration M Hard coded to 0x000D Motion Sensor 0x0002 Zone Status Uint16 M The following bits are supported Bit0 Alarm 1 Bit2 Tamper Bit3 Battery Bit4 Supervision reports Bit5 Restore reports Bit6 Trouble Bit9 Battery...

Page 12: ...D of each zone stays fixed until that zone is unenrolled 4 2 1 2 Commands The IAS Zone cluster has 2 commands as server Id Name Payload Man Opt Relevance and ref 0x00 Zone Status Change Notification Uint16 bit mask M The status is report to the coordinator every 5 min 0x01 Zone Enroll Request Bits 16 16 M Data type 16 bit enum UINT16 Field name Zone type Manufacturer code Init sequence when the de...

Page 13: ... Battery bit is set high and Zone Status is transmitted to the coordinator Bit9 When the battery is defect the sensitivity of the motion detector is reduced to avoid false alarms Therefore when this bit is true it is highly recommended that the battery is changed 4 2 2 Power Configuration Cluster id 0x0001 The power configuration cluster is described in ZigBee Cluster Library Specification 4 2 2 1...

Page 14: ...aged by the controller 4 2 3 1 Attribute Id Name Type Range Man Opt Relevance and ref 0x0000 Check inInterval Uint32 0x00 0xFF M Default value is 1 hour 0x0001 LongPoll Interval Uint32 M Default value is disabled 0x0002 ShortPollIntervall Uint16 M Default value is 3 seconds 0x0003 FastPollTimeout Uint16 M Default value is 5 minutes Start up auto scan for client poll control cluster on the coordina...

Page 15: ...2 Type range O 0x0003 CurrentZigBeeStackVersion Uint16 Type range O 0x0004 DownloadedFileVersion Uint32 Type range O 0x0005 DownloadedZigBeeStackVersion Uint16 Type range M 0x0006 ImageUpgradeStatus 8 bit enum 0x00 to 0xFF O 0x0007 Manufacturer ID Uint16 Type range O 0x0008 Image Type ID Uint16 Type range O 0x0009 MinimumBlockRequestDelay Uint16 Type range O Above attribute description is to be fo...

Page 16: ...Motion Sensor MOSZB 130 Technical manual Develco Products A S Olof Palmes Allé 40 http develcoproducts com DK 8200 Aarhus N info develcoproducts com 16 4 2 4 3 OTA Upgrade Messages Diagram ...

Page 17: ...will periodically update its clock by synchronizing through this cluster 0x0001 TimeStatus 8 bit bitmap 00000xxx M 4 2 6 Binary Input Cluster Cluster id 0x000F The Binary input cluster is described in ZigBee Cluster Library Specification 4 2 6 1 Attribute Id Name Type Range Man Opt Relevance and ref 0x001C Description String Motion O 0x0051 OutOfService Bool False 0 or True 1 M If True PresentValu...

Page 18: ...configure the logic module 4 3 1 Occupancy sensing Cluster id 0x0406 The occupancy sensing cluster is described in ZigBee Cluster Library Specification section 4 8 4 3 1 1 Attribute Id Name Type Range Man Opt Relevance and ref 0x0000 Occupancy 8 bit Bitmap 0000000x M Reporting is supported 0x0001 Occupancy Sensor Type 8 bit Enumeration 0x00 0xfe M Hard coded to PIR sensor 0x0010 PIROccupiedTo Unoc...

Page 19: ... the temperature sensor input Logic module If Temperature ArmThreshold_MaxTemperature or Temperature ArmThreshold_MinTemperature Temperature measure value Cluster ID 0x0402 Attribute ID 0x0000 Occupancy state Occupancy state Use case Energy savings in an office building The device is installed to obtain energy savings in an office with an air condition A ZigBee relay is installed to turn on the ai...

Page 20: ... controls the occupancy sensor signal base on the user defined settings for the illumination sensor input Logic module If Illumination is X TargetLevel Illuminance measure value Cluster ID 0x0400 Attribute ID 0x0000 Occupancy state Occupancy state Use case Energy savings in an office building The device is installed to obtain energy savings in an office controlling the light A ZigBee relay is inst...

Page 21: ... configured 0x0001 MinMeasuredValue Sint16 0 M 0x0002 MaxMeasuredValue Sint16 5000 M 4 4 1 1 1 MeasuredValue The attribute is configured with the following default ZCL configure reporting setting Min Reporting Interval 0x003C 60 sec Max Reporting Interval 0x0258 600 sec Reportable Change 0x000A 0 1 C If the temperature value is stable it will be send every 10 minutes If the temperature changes mor...

Page 22: ...t16 0x0002 0xfffd M 0x0002 MaxMeasuredValue Uint16 0x0001 0xfffe M 0x0004 LightSensorType 8 bit Enumeration 0x00 0xff O 4 5 1 1 1 MeasuredValue The attribute is configured with the following default ZCL configure reporting setting Min Reporting Interval 0x0000 0 sec Max Reporting Interval 0x0258 600 sec Reportable Change 0xFFFF Disabled The illumination value is sent every 10 minutes according to ...

Page 23: ... modes the state is indicated by a number of 100ms blinks on the LED The device is supporting the ZigBee standardized EZ mode Commissioning 5 1 1 EZ mode Initiator If the devices is not on the network EZ Mode Network Steering is invoked when the user enter this menu The led blinks once every 1 sec until the devices has joined the network If the device was already on the network it will broadcast t...

Page 24: ...until identify mode is stopped or after the EZ mode time has expired If the user enters the menu again another 3 minutes is started 5 1 3 Factory reset To allow a device to join a network one either has to power up a device that has not previously joined a network or push the button until the Reset To Factory default mode is indicated and subsequently release the button This will cause the device ...

Page 25: ...ime a scan mode 2 will be used after scan mode 1 has expired Scan mode 1 it will only be executed one time when the device is powered If the user invokes EZ mode it will start scanning the next 3 minutes In section 5 MMI it is explained how to put the device into a join or leave network mode Network settings are stored in NV memory are after a power cycle the device re join the same network If the...

Page 26: ...de Radio off 15 minutes Scan mode 2 Scan current ch 3 times Scan remaining 15 ch 1 time Sleep mode MCU is in sleep mode Radio off 15 minutes Scan mode 2 Scan current ch 3 times Scan remaining 15 ch 1 time 6 3 Low battery The current battery voltage can be read from the power configuration cluster described in section 4 3 1 The attribute BatteryVoltage is measuring the battery voltage in units of 1...

Page 27: ... Output power 3 dBm EU Environment Operation temperature 0 to 50 C Occupancy Range 6m View angle 45 up down left right Off time Configurable 2 s 65 000 s Light Resolution 3 to 70 000 Lux Common light source illuminance lux Street light 20 Dusk 1 to 100 Living room 50 to 200 Office 200 to 600 Operating room 5 k to 10 k Cloudy 2 k to 10 k Hazy 25 k to 50 k Bright sun 50 k to 100 Tolerance 10 000 lux...

Page 28: ...velcoproducts com DK 8200 Aarhus N info develcoproducts com 28 8 Contact Information Technical support Please contact Develco Products for support products develcoproducts com Sales Please contact Develco Products for information on prices availability and lead time info develcoproducts com ...

Reviews: