31
E
LECTRO
V
AP
KIT MC
Maintenance - Valves
The inlet valve should be maintained every 6
months as a minimum and after 50 hours operation.
Isolate the water supply and remove the water supply
hose from the valve.
Disconnect the electrical wires from the coil.
Untighten the collar clamp and remove the water feed
hose.
Unscrew the black nut
1
and lay it on the cylinder
compartment tray.
Take the valve out and remove the basket filter from the
base of the valve with a pair of long nose pliers. Pull the
coil out with a flat screw driver.
Wash the basket filter under clean water to remove any
dirt and debris.
Replace whole valve if cleaning is not practical or
replace coil if necessary.
Assemble in reverse order taking care to replace collar
clamp if necessary.
Ensure that everything is correctly assembled and switch the
humidifier on.
Ensure that all the clamps are properly tightened whenever
the humidifier is maintained.
1
INLET VALVE MAINTENANCE